Table of Contents Table of Contents
Previous Page  90 / 210 Next Page
Information
Show Menu
Previous Page 90 / 210 Next Page
Page Background

90

0442 35

0442 68

0442 71

IP 2X or IP XXB up to 400 VA

IP XXA above 400 VA - IK 04

Conform to IEC/EN 61558-2-2 and 2-4 or 2-6

UL506 and CSA C22-2-N°66

Products suitable for building into equipment conforming to EN 61131-2, EN 60204-1 and EN 61439 standards

Insulated covers up to 1 000 VA provided

Interference/disturbance filter included

Screw fix to mounting plate or clip on to DIN rail up to 250 VA

Supplied with 0V/Earth connection link up to 1 000 VA

Pack

Cat. Nos.

Single phase

Primary : 230-400 V ± 15 V

Secondary : 24-48 V

Supplied with 2 links

Power in VA

Admissible

instantaneous

according to according

power

IEC and CSA

to UL

at cos

ϕ

= 0·5

1

0442 31

40

40

52

1

0442 32

63

63

87

24 V 48 V

1

0442 33

100

100

150

1

0442 34

160

140

250

1

0442 35

250

210

420

1

0442 36

400

300

900

1

0442 37

630

500

1 700

1

0442 38

1 000

700

2 000

1

0442 39

1 600

700

8 500

1

0442 40

2 500

1 400

3 300

Multiple fixing possibilities

DIN rail

p. 26

Lina 12 . 5 plates

p. 23

Lina 25 plates

p. 23

Secondary protection

Transformers can be protected by a gG type

fuse

p. 76

or by a C type circuit breaker

p. 56

Pack

Cat. Nos.

Single phase

Safety isolating transformers

Primary : 230-400 V ± 15 V

Secondary : 115-230 V

Supplied with 2 links

Power in VA

Admissible

instananeous

according to according

power

IEC and CSA

to UL

at cos

ϕ

= 0·5

1

0442 61

40

40

50

1

0442 62

63

63

86

1

0442 63

100

100

150

1

0442 64

160

140

250

1

0442 65

250

210

430

1

0442 66

400

300

1 200

1

0442 67

630

500

1 600

1

0442 68

1 000

700

2 000

1

0442 69

1 600

700

6 100

1

0442 70

2 500

1 300

7 100

1

0442 71

4 000

2 400

11 400

Dimensions and technical information

p. 91

control, signalling and safety isolation transformers

open type single phase

Modular transformers

p. 102