![Show Menu](styles/mobile-menu.png)
![Page Background](./../common/page-substrates/page0089.jpg)
87
n
Protection index
Class II
0
IP 2X protection against direct contact
Mechanical characteristics
• Environmental conditions
Operating temperature : –5 °C to +40 °C
n
Dimensions
0043 82
0043 83
s004382
s004383
s004385
Pack
Cat. Nos.
Changeover switches
Conform to IEC 60669-1
Breaking capacity AC 22 A according to BS EN 60947-3
Nominal rating
No. of 17·5 mm
(A)
modules
Two way - 250 V
±
10
0043 82
20
1
Double two way - 400 V
±
5
0043 83
20
2
Two way with centre point - 250 V
±
10
0043 85
20
1
n
Installation
• Mounting
- on symmetrical rail EN 50-022
- with Ø3 mm screw on plate using ends of released claws
- supply via the top or the bottom
- operating position : vertical
• Wiring
Conductors permitted
Flexible with end caps
1 . 5 to 4 mm
2
Rigid
1 . 5 to 4 mm
2
Tools required :
Flat blade screwdriver
Ø4 mm
Posidrive screwdriver
Pz 1
Tightening torque
Min.
0 . 8 Nm
Max.
1 . 8 Nm
Recommended
1 . 2 Nm
B
94
83
45
44
60
68
74
changeover switches
Dimensions and technical information
opposite
Cat. Nos.
B
0043 82/85
17 . 7
0043 83
35 . 6
Accessories
Padlocking
2
4063 03 Support for one
Ø
5 mm padlock
3
4063 13
Ø
5 mm shackle type padlock
a093505a