Protection index

Class II

0

IP 2X protection against direct contact

Mechanical characteristics

• Environmental conditions

Operating temperature : –5 °C to +40 °C

n

Dimensions

0043 82

0043 83

s004382

s004383

s004385

Pack

Cat. Nos.

Changeover switches

Conform to IEC 60669-1

Breaking capacity AC 22 A according to BS EN 60947-3

Nominal rating

No. of 17·5 mm

(A)

modules

Two way - 250 V

±

10

0043 82

20

1

Double two way - 400 V

±

5

0043 83

20

2

Two way with centre point - 250 V

±

10

0043 85

20

1

n

Installation

• Mounting

- on symmetrical rail EN 50-022

- with Ø3 mm screw on plate using ends of released claws

- supply via the top or the bottom

- operating position : vertical

• Wiring

Conductors permitted

Flexible with end caps

1 . 5 to 4 mm

2

Rigid

1 . 5 to 4 mm

2

Tools required :

Flat blade screwdriver

Ø4 mm

Posidrive screwdriver

Pz 1

Tightening torque

Min.

0 . 8 Nm

Max.

1 . 8 Nm

Recommended

1 . 2 Nm

B

94

83

45

44

60

68

74

changeover switches

Dimensions and technical information

opposite

Cat. Nos.

B

0043 82/85

17 . 7

0043 83

35 . 6

Accessories

Padlocking

2

4063 03 Support for one

Ø

5 mm padlock

3

4063 13

Ø

5 mm shackle type padlock

a093505a