Table of Contents Table of Contents
Previous Page  86 / 210 Next Page
Information
Show Menu
Previous Page 86 / 210 Next Page
Page Background

86

Dimensions

Front handle

63 to 160 A

Direct

External

Conform to standards BS EN 60947-3, EN / IEC 60947-3, VDE 0660,

NBN EN 60947-3, CNOMO E03 - 15-611 R, Bureau Veritas approved

Glass fibre reinforced insulating casing, self-extinguishing at 960 °C

(IEC EN 60695-2-1)

Handle can be padlocked in open position using 1 to 3 padlocks Ø6 mm

n

Electrical characteristics

n

Example of mounting with Vistop 100 to 160 A

Front handle

63 A

100 A, 125 A, 160 A

3P and 4P

3P 4P

C

125

133 160

C

1

17 . 7

26 . 7

C

2

90

91

63

45

78

83

C2

22

44

6

60

74

98

min. 114 - max. 523

C

C1

Thermal

rating (Ith)

63 A

100 A

125 A

160 A

Terminals

cage

cage

cage

cage

Connection

Cu (flexible)

4 to 35

2

4 to 50 mm

2

Cu (rigid)

4 to 50

2

4 to 70 mm

2

Insulating voltage

(Ui)

690 V

±

800 V

±

800 V

±

800 V

±

Impulse resistant

voltage (Uimp)

8 kV

8 kV

8 kV

8 kV

AC 22 A

1

400 V

63 A (35 kW) 100 A (55 kW) 125 A (70 kW) 160 A (88 kW)

AC 23 A

1

500 V

63 A (44 kW) 100 A (69 kW) 125 A (87 kW) 160 A (110 kW)

690 V

40 A (38 kW) 100 A (96 kW) 125 A (120 kW) 125 A (120 kW)

DC 22 A/250 V

1, 2

63

100

125

125

DC 23 A/250 V

1, 2

63

100

125

125

Breaking capacity

(Icu) (kA peak)

15

15

15

15

1 s resistant current

(kA rms) (Icw)

2 . 5

3 . 5

3 . 5

3 . 5

Icc

with fuses

100

100

100

80

(kA rating)

Fuse rupture

63 A

100 A (gG)

125 A (gG)

160 A (gG)

capacity

63 A (aM)

3

125 A (aM)

3

125 A (aM)

Short circuit capacity

(kA prospective peak)

7

12

12

12

(Icm)

Mechanical

endurance

> 30000

> 30000

> 30000

> 30000

(No. of operations)

IP 2X B

Index of protection

(IP 3X C under

IP 2X B (IP 3X C under front plate)

front plates)

from 10 mm

2

from 6 mm

2

1 : Test according to IEC 60947-3

AC 22 A / DC 22 A : resistive motor breaking

AC 23 A / DC 23 A : inductive motor breaking

2 : No of breaking contacts : 2

3 : 100 A (aM) with blade type cartridge fuses

Isolating

switch Vistop

Front external handle

Cat. No. 0227 32

Vistop™ isolating switches

63 to 160 A (continued)