Table of Contents Table of Contents
Previous Page  84 / 210 Next Page
Information
Show Menu
Previous Page 84 / 210 Next Page
Page Background

84

AC 23 A according to BS EN 60947-3 and IEC 60947-3, AC 22 A for 125 A

Double break contacts

Visible contact indicator

isolating switches

DX

3

-IS

16 to 125 A

Dimensions

p. 103

Technical information

opposite

Pack

Cat. Nos.

Isolating switches

Grey handle

Can be equipped with 1 DX

3

signalling auxiliary (p. 58)

Lock in open and closed position with locking device

Cat. No. 4063 03 and Ø 5 mm padlock Cat. No. 4063 13

Label holder for circuit indentification

1P - 250 V

±

Nominal rating In (A)

Number of modules

10

4064 00

16

1

10

4064 01

20

1

10

4064 03

32

1

10

4064 11

40

1

10

4064 12

63

1

10

4064 23

100

1

2P - 400 V

±

10

4064 31

16

1

10

4064 32

20

1

10

4064 34

32

1

5

4064 40

40

2

5

4064 41

63

2

5

4064 53

63 with red handle

2

5

4064 55

100 with red handle

2

5

4064 50

125

2

2P with indicator - 400 V

±

Supplied with lamp

Do not accept auxiliaries

10

4064 36

20

1

10

4064 38

32

1

3P - 400 V

±

5

4064 57

20

2

5

4064 59

32

2

1

4064 60

40

3

1

4064 61

63

3

1

4064 75

100 with red handle

3

1

4064 70

125

3

4P - 400 V

±

5

4064 77

20

2

5

4064 79

32

2

1

4064 80

40

4

1

4064 81

63

4

1

4064 95

100 with red handle

4

1

4064 90

125

4

4064 81

4064 59

NEW

n

DX

3

-IS isolating switches

Electrical characteristics

1 : test conditions according to IEC 60947-3

AC 22 A : combined motor/resistor breaking with frequent operations

Thermal rating (Ith)

16 - 40 A

0.5 module/pole

40 - 63 A

1 module/pole

100 - 125 A

1 module/pole

Terminals

Cage

Cage

Cage

Connection

flexible

1.5 to 10 mm

2

1.5 to 16 mm

2

1.5 to 25 mm

2

1.5 to 35 mm

2

4 to 35 mm

2

4 to 50 mm

2

rigid

Insulation voltage (Hi)

500 V

±

500 V

±

500 V

±

Impulse withstand voltage

(Uimp)

6 kV

6 kV

6 kV

Category of use

1

AC 22 A

AC 22 A

AC 22 A

Short time withstand

current (Icw)

750 A

2000 A

2500 A

Short-circuit making

capacity (Icm)

1500 A

3000 A

3700 A

No. of electrical operations

30000

20000

5000

Protection index

IP 2X wired

IP 2X wired

IP 2X wired

Accessories

Padlocking

2

4063 03 Support for one

Ø

5 mm padlock for

DX

3

MCBs and RCDs or isolating switches

3

4063 13

Ø

5 mm shackle type padlock

Sealable screw cover - 4 separable poles

2

4063 04 For DX

3

isolating switches, 1 module per pole

Insulating shields

For DX

3

isolating switches,

1 module per pole

1

4063 05 Pole insulating shield (set of 6)

a093505a