96
Filtered power supplies for PLCs and other equipment requiring a voltage
of 12 V DC or 24 V DC
Include :
• twin output terminals for ease of connection
• safety transformer with interference filtration
• fuse protection on output
• green LED output voltage indicator
• capacitor in filtered range
Supplied with a connection link for quick connection between - and
T
up to 15 A
Fixing options :
- clip directly to DIN rail up to 24 W
- clip on or screw fixing up to 120 W
- screw fixing only above 120 W
n
Dimensions
Cat. Nos.
A (mm)
B (mm)
C (mm)
F x G (mm)
Ø (mm)
Weight
Width
Depth
Height
Fixing ctrs
(Kg)
0470 01
68
98
88
DIN
4
–
1·00
0470 02
93
121
105
DIN
4
4·6
2·45
0470 03
105
135
115
DIN
4
4·6
3·60
0470 04
126
186
175
75 x 150
5·5
6·35
0470 20
68
98
88
DIN
4
–
1·00
0470 21
68
98
88
DIN
4
–
1·00
0470 22
93
121
105
DIN
4
4·6
2·45
0470 23
105
135
115
DIN
4
4·6
3·60
0470 24
126
186
175
75 x 150
5·5
6·40
0470 25
126
206
175
75 x 150
5·5
7·60
0470 24
0470 23
Pack
Cat. Nos.
Single phase filtered
12 V
=
output
230-400 V ± 15 V
±
(input) / 12 V
=
(output)
Terminal capacity (mm
2
)
Power
Current rating
Flexible cable
(W)
(A)
Input
Output
1
0470 01
12
1
6
6
1
0470 02
30
2·5
6
6
1
0470 03
60
5
6
6
1
0470 04 120
10
6
6
24 V
=
output
230-400 V ± 15 V
±
(input) / 24 V
=
(output)
Terminal capacity (mm
2
)
Power
Current rating
Flexible cable
(W)
(A)
Input
Output
1
0470 20
12
0·5
6
6
1
0470 21
24
1
6
6
1
0470 22
60
2·5
6
6
1
0470 23
120
5
6
6
1
0470 24
240
10
6
6
1
0470 25
360
15
6
6
F
B
A
C
G
04791-65791c.eps
B
G
C
F
A
046925-4369c.eps
Cat. Nos. 0470 01/02/03
and 0470 20/21/22/23
Cat. Nos. 0470 04/24/25
Indice protection-1061s
n
Technical information
Conform to IEC / EN 61558-2-6, UL 60950
CAN/CSA C22.2 N° 60 950.00
Products are compatible with EN 61131-2, EN 60204 and
EN 61439 apparatus
Input voltage : 230/400 V
±
±15 V single phase 50/60 Hz - Class I
Output voltage : 12 V
=
or 24 V
=
Insulation voltage : Input/Output 4 510 V
Input/Earth 2 260 V
Output/Earth 500 V
Max. ambient temperature without derating : 60 °C
Ripple factor : <3 %
Cooling by natural convection
Integral fuse protection on output
Can be fixed to symmetrical rail
4
7·5 mm or 15 mm depth EN 60715
Screw fix only Cat. Nos. 0470 04/24 and 25
Screw fix or clip on to DIN rail Cat. Nos. 0470 02/03/22 and 23
Supplied with a connection link for quick connection between terminals
and earth
Note :
To conform to UL, product must be mounted in the vertical
position (mounting against support) for Class A ambient
temperature rating 25 °C
n
Operating diagram
Operating current up to 15 A
400 V
230 V
-15 V
0
+15 V
+
+
046901-6825s.eps
filtered power supplies
open type single phase
Dimensions and technical information
opposite and p. 97
DX
3
MCBs
p. 56-57
Fuses
p. 76-77