Table of Contents Table of Contents
Previous Page  618 / 759 Next Page
Information
Show Menu
Previous Page 618 / 759 Next Page
Page Background mkelectric.co.uk

618

CABLE MANAGEMENT

PERIMETER AND

DISTRIBUTION

CABLE CAPACITY

TYPE OF

CONDUCTOR SIZE

CABLE

FACTOR

COMPARTMENT 1

COMPARTMENT 2

COMPARTMENT (X)

FULL TERM CSA (MM

2

)

742

1431

3035

TERM AT 45% FILL (MM

2

)

333

643

1365

POWER CABLES

NUMBER OF CABLES AT 45% FILL

PVC

stranded

1.5mm

2

8.6

38

74

158

2.5mm

2

12.6

26

51

108

4mm

2

16.6

20

38

82

6mm

2

21.2

15

30

64

DATA CABLES

NUMBER OF CABLES AT 45% FILL (A) AND FULL CAPACITY (B)

A

B

A

B

A

B

Cat 5E UTP 5.5mm dia.

30.2

11

24

21

47

45

100

Cat 5E STP 6.0mm dia.

36.0

9

20

17

39

37

84

Cat 6 UTP 6.5mm dia.

42.2

7

17

15

33

32

71

Cat 6 STP 7.0mm dia.

49.0

6

15

13

29

27

61

Cat 7

8.0mm dia

64.0

5

11

10

22

21

47

Prestige 3D Technical

– Compact

45mm

160mm

45mm

140mm

(X)

2

1

1

(X)

1

Dado

Extended Dado

* Compartment (X) dimensions and capacity are given as guide only for instances where trunking is used for cable routing e.g. vertical drops/risers.

VCT140

Data Trunking System

Dimensions (mm)

PROFILES

Compartment CSA mm

2

1 = 742

2 = 1431

*(X) = 3035

ASSEMBLY

Dado = 1.20 Kg/m

Extended Dado = 1.35 Kg/m

WALL THICKNESS

VCT100 = 1.7mm

VCT110 = 1.7mm

VCT120 = 1.7mm

VCT140 = 2.0mm

VCT160 = 2.0mm

VCT110

VCT100

VCT110

VCT140

VCT160

VCT110

VCT100

VCT120