CI insulated enclosures
Standards, measured values
2010
CA08103002Z-EN
www.eaton.comInsulated distribution boards
20/85
InsulateddistributionboardsStandards,measured values
CI…
General
Components
Components of switchgear assemblies are type-tested. They are suitable for
self-assembly of switchgear installations, distribution boards and control panels.
Mounting units
The reference values stated apply to the basic elements of the distribution board.
For devices fitted, terminals etc., their reference and rated values apply.
Standards
TTA – Type Tested Assemblies
IEC/EN 60439-1, VDE 0660 Part 500
Low-voltage fuses
IEC/EN 60269, VDE 0636
Type test
VDE 0660 Part 500, IEC/EN 60439-1
Creepage and clearance distances
III/3 to IEC/EN 60439-1
Flammability characteristics - Glow rod test
VDE 0304 Part 3 level IIb, level IIb to IEC 60707
Regulations for fire-resistance tests of electrical
products, their modules and components, glow
wire test
VDE 0471 Part 2
Operating and environmental conditions to
VDE 0660 Part 500
Ambient temperature
Mean value over 24 hours
°C
35
Limit values
°C
-5…40
Indoor installation
Relative humidity
at 20 °C
% 90
at 40 °C
% 50
Installation altitude
m
max. 2000
Protection type
CI enclosure
IP65
KST cable entry from below
IP65
KST cable entry from above
IP64
Cable entry open
IP00
Modular grid (enclosure basic dimensions)
mm 25 (DIN 43660)
Color
Base
RAL 7032, pebble grey
Cover
Transparent, opaque or RAL 7032, pebble grey
CI...-NA: Transparent cover, opaque
Surface protection with metals
Galvanized, passivated
Radiated heat dissipation
→Page 20/86
Electrical characteristics
Busbar system
Rated operating voltage
U
e
V AC 690
690
690
690
690
690
Rated insulation voltage
AC
U
i
V AC 690
690
690
690
690
690
DC
U
i
V DC 800
800
800
800
800
800
Rated operational current
I
e
A
160
250
400
630
1000
1600
Rated short-time withstand current
t = 0.1 s cos ϕ = 0.2
I
cw
kA
20
25
35
40
80
80
Rated short-time withstand current t = 1 s I
cw
kA
4
7
14
28
50
66
Rated peak withstand current
I
pk
kA
40
52.5
73.5
84
176
176
Distance between busbar supports
mm ≦ 375
≦ 375
≦ 375
≦ 375
≦ 375
≦ 375
WW...-ID, WS...-ID