Background Image
Table of Contents Table of Contents
Previous Page  124 / 439 Next Page
Information
Show Menu
Previous Page 124 / 439 Next Page
Page Background

5/120

Contactors

Comfort devices and standard devices greater than 170 A

2010

CA08103002Z-EN

www.eaton.com

AC voltage

AC-4 operation

Rated operational current AC -4 open,

50 – 60

Hz, 3 pole

220/230

V

I

e

A

136

164

200

240

296

360

360

240

V

I

e

A

136

164

200

240

296

360

360

380/400

V

I

e

A

136

164

200

240

296

360

360

415

V

I

e

A

136

164

200

240

296

360

360

440

V

I

e

A

136

164

200

240

296

360

360

500

V

I

e

A

136

164

200

240

296

360

360

660/690

V

I

e

A

110

120

200

170

296

296

296

1000

V

I

e

A

55

55

76

76

95

95

95

Rated operational power

220/230

V

P

kW 41

51

62

75

92

112

112

240

V

P

kW 45

54

68

82

101

122

122

380/400

V

P

kW 75

90

110

132

160

200

200

415

V

P

kW 80

96

117

142

176

216

216

440

V

P

kW 85

102

125

150

186

229

229

500

V

P

kW 96

116

143

172

214

260

260

660/690

V

P

kW 102

110

189

160

283

344

344

1000

V

P

kW 77

77

108

109

132

132

132

Capacitor operation

Individual compensation rated operational

current I

e

of alternating current capacitor

Open

To 525 V

A

220

220

220

307

307

307

307

690

V

A

133

133

133

177

177

177

177

Max. peak inrush current

x I

e

30

30

30

30

30

30

30

Component lifespan

c (contacts)

x 10

6

0.1

0.1

0.1

0.1

0.1

0.1

0.1

Max. operating frequency

Ops/h 200

200

200

200

200

200

200

DC voltage

Operations

→Engineering Page 5/96

Rated operational current I

e

open

DC-1 operation

60

V

I

e

A

300

300

300

400

400

400

400

110

V

I

e

A

300

300

300

400

400

400

400

220

V

I

e

A

300

300

300

400

400

400

400

440

V

I

e

A

11

11

11

11

11

11

11

DC-3 operation

60

V

I

e

A

300

300

300

400

400

400

400

110

V

I

e

A

300

300

300

400

400

400

400

220

V

I

e

A

300

300

300

400

400

400

400

DC-5 operation

60

V

I

e

A

300

300

300

400

400

400

400

110

V

I

e

A

300

300

300

400

400

400

400

220

V

I

e

A

300

300

300

400

400

400

400

Current heat loss (3 pole)

Current heat loss at I

th

W 34

45

55

37

58

113

130

Current heat loss at I

e

to AC-3/400 V

W 16

23

28

21

37

58

78

Contactors

DILM185A DILM225A DILM250 DILM300A DILM400 DILM500 DILM570

DILM185...DILM1600, DILH