5/120
Contactors
Comfort devices and standard devices greater than 170 A
2010
CA08103002Z-EN
www.eaton.comAC voltage
AC-4 operation
Rated operational current AC -4 open,
50 – 60
Hz, 3 pole
220/230
V
I
e
A
136
164
200
240
296
360
360
240
V
I
e
A
136
164
200
240
296
360
360
380/400
V
I
e
A
136
164
200
240
296
360
360
415
V
I
e
A
136
164
200
240
296
360
360
440
V
I
e
A
136
164
200
240
296
360
360
500
V
I
e
A
136
164
200
240
296
360
360
660/690
V
I
e
A
110
120
200
170
296
296
296
1000
V
I
e
A
55
55
76
76
95
95
95
Rated operational power
220/230
V
P
kW 41
51
62
75
92
112
112
240
V
P
kW 45
54
68
82
101
122
122
380/400
V
P
kW 75
90
110
132
160
200
200
415
V
P
kW 80
96
117
142
176
216
216
440
V
P
kW 85
102
125
150
186
229
229
500
V
P
kW 96
116
143
172
214
260
260
660/690
V
P
kW 102
110
189
160
283
344
344
1000
V
P
kW 77
77
108
109
132
132
132
Capacitor operation
Individual compensation rated operational
current I
e
of alternating current capacitor
Open
To 525 V
A
220
220
220
307
307
307
307
690
V
A
133
133
133
177
177
177
177
Max. peak inrush current
x I
e
30
30
30
30
30
30
30
Component lifespan
c (contacts)
x 10
6
0.1
0.1
0.1
0.1
0.1
0.1
0.1
Max. operating frequency
Ops/h 200
200
200
200
200
200
200
DC voltage
Operations
→Engineering Page 5/96
Rated operational current I
e
open
DC-1 operation
60
V
I
e
A
300
300
300
400
400
400
400
110
V
I
e
A
300
300
300
400
400
400
400
220
V
I
e
A
300
300
300
400
400
400
400
440
V
I
e
A
11
11
11
11
11
11
11
DC-3 operation
60
V
I
e
A
300
300
300
400
400
400
400
110
V
I
e
A
300
300
300
400
400
400
400
220
V
I
e
A
300
300
300
400
400
400
400
DC-5 operation
60
V
I
e
A
300
300
300
400
400
400
400
110
V
I
e
A
300
300
300
400
400
400
400
220
V
I
e
A
300
300
300
400
400
400
400
Current heat loss (3 pole)
Current heat loss at I
th
W 34
45
55
37
58
113
130
Current heat loss at I
e
to AC-3/400 V
W 16
23
28
21
37
58
78
Contactors
DILM185A DILM225A DILM250 DILM300A DILM400 DILM500 DILM570
DILM185...DILM1600, DILH