16/12
Total Solution to Earthing & Lightning Protection |
9AKK106354A3360
16
Technical reference
IEC/BS EN 62305-3 - Physical damage to structures & life hazard
Non-conventional air termination systems
A lot of technical (and commercial) debate has raged over
the years regarding the validity of the claims made by
the proponents of such systems. This topic was discussed
extensively within the technical working groups that compiled
IEC/BS EN 62305. The outcome was to remain with the
information housed within this standard.
IEC/BS EN 62305 states unequivocally that the volume or
zone of protection afforded by the air termination system
(e.g. air rod) shall be determined only by the real physical
dimension of the air termination system. This statement is
reinforced within the 2011 version of BS EN 62305, by being
incorporated in the body of the standard, rather than forming
part of an Annex (Annex A of IEC/BS EN 62305-3:2006).
Typically if the air rod is 5 m tall then the only claim for
the zone of protection afforded by this air rod would be based
on 5 m and the relevant class of LPS and not any enhanced
dimension claimed by some nonconventional air rods.
There is no other standard being contemplated to run
in parallel with this standard IEC/BS EN 62305.
Natural components
When metallic roofs are being considered as a natural air
termination arrangement, IEC/BS EN 62305 offers
guidance on the minimum thickness and type of material
under consideration, as well as additional information
if the roof has to be considered puncture proof from a
lightning discharge (see Table 10).
Table 11:
Typical values of the distance between down conductors according
to the Class of LPS (IEC/BS EN 62305-3 Table 4)
Class of LPS
Typical distances
I
10 m
II
10 m
III
15 m
IV
20 m
Down conductors
Down conductors should within the bounds of practical
constraints take the most direct route from the air termination
system to the earth termination system. The greater the
number of down conductors the better the lightning current
is shared between them. This is enhanced further by
equipotential bonding to the conductive parts of the structure.
Lateral connections sometimes referred to as coronal bands
or ring conductors provided either by fortuitous metalwork or
external conductors at regular intervals are also encouraged.
The down conductor spacing should correspond with the
relevant class of LPS (see Table 11).
There should always be a minimum of two down conductors
distributed around the perimeter of the structure. Down
conductors should wherever possible be installed at each
exposed corner of the structure as research has shown these
to carry the major part of the lightning current.
Table 10:
Minimum thickness of metal sheets or metal pipes in air termination
systems (IEC/BS EN 62305-3 Table 3)
Class of LPS
Material
Thickness
(1)
t Thickness
(2)
t’
I to IV
Lead
–
2.0 mm
Steel (stainless, galvanized) 4 mm
0.5 mm
Titanium
4 mm
0.5 mm
Copper
5 mm
0.5 mm
Aluminium
7 mm
0.65 mm
Zinc
–
0.7 mm
(1)
Thickness t prevents puncture, hot spot or ignition
(2)
Thickness t’ only for metal sheets if it is not important to prevent puncture, hot spot or
ignition problems