Total Solution to Earthing & Lightning Protection |
9AKK106354A3360
16/9
16
Technical reference
IEC/BS EN 62305-3 - Physical damage to structures & life hazard
The main body of this part of the standard gives guidance on
the design of an external Lightning Protection System (LPS),
internal LPS and maintenance and inspection programmes.
Lightning Protection System (LPS)
IEC/BS EN 62305-1 has defined four Lightning Protection
Levels (LPLs) based on probable minimum and maximum
lightning currents. These LPLs equate directly to classes of
Lightning Protection System (LPS).
The correlation between the four levels of LPL and LPS is
identified in Table 7. In essence, the greater the LPL, the
higher class of LPS is required.
External LPS design considerations
The lightning protection designer must initially
consider the thermal and explosive effects caused at
the point of a lightning strike and the consequences to
the structure under consideration. Depending upon
the consequences the designer may choose either of
the following types of external LPS:
–– Isolated
–– Non-isolated
External LPS design considerations
An Isolated LPS is typically chosen when the structure is
constructed of combustible materials or presents a risk
of explosion.
Conversely a non-isolated system may be fitted where
no such danger exists.
An external LPS consists of:
–– Air termination system
–– Down conductor system
–– Earth termination system
These individual elements of an LPS should be connected
together using appropriate lightning protection components
(LPC) complying (in the case of BS EN 62305) with
IEC/BS EN 62561 series. This will ensure that in the event
of a lightning current discharge to the structure, the
correct design and choice of components will minimize
any potential damage.
Air termination system
The role of an air termination system is to capture the
lightning discharge current and dissipate it harmlessly to
earth via the down conductor and earth termination system.
Therefore it is important to use a correctly designed air
termination system.
IEC/BS EN 62305-3 advocates the following, in any
combination, for the design of the air termination:
–– Air rods (or finials) whether they are free-standing masts or
linked with conductors to form a mesh on the roof
–– Catenary (or suspended) conductors, whether they are
supported by free-standing masts or linked with
conductors to form a mesh on the roof
–– Meshed conductor network that may lie in direct contact
with the roof or be suspended above it (in the event that it
is of paramount importance that the roof is not exposed to
a direct lightning discharge)
The standard makes it quite clear that all types of air
termination systems that are used shall meet the
positioning requirements laid down in the body of the
standard. It highlights that the air termination
components should be installed on corners, exposed
points and edges of the structure.
The three basic methods recommended for
determining the position of the air termination
systems are:
–– The rolling sphere method
–– The protective angle method
–– The mesh method
These methods are detailed over the following pages.
Table 7:
Relation between Lightning Protection Level (LPL) and Class of LPS
(IEC/BS EN 62305-3 Table 1)
LPL
Class of LPS
I
I
II
II
III
III
IV
IV
IEC/BS EN 62305-3. This part of the suite of standards deals with protection
measures in and around a structure.