Total Solution to Earthing & Lightning Protection |

9AKK106354A3360

16/7

16

Technical reference

IEC/BS EN 62305-1 - Lightning protection zones (LPZ)

Lightning protection zones (LPZ)

The concept of the Lightning Protection Zone (LPZ)

was introduced within IEC/BS EN 62305 particularly to

assist in determining the protection measures required

to establish protection measures to counter Lightning

Electromagnetic Impulse (LEMP) within a structure.

The general principle is that the equipment requiring

protection should be located in an LPZ whose

electromagnetic characteristics are compatible with the

equipment stress withstand or immunity capability.

The concept caters for external zones, with risk of direct

lightning strike, or partial lightning current occurring

(LPZ 0) and levels of protection within internal zones

(LPZ 1 & LPZ 2).

In general the higher the number of the zone (LPZ 2;

LPZ 3 etc) the lower the electromagnetic effects expected.

Typically, any sensitive electronic equipment should be

located in higher numbered LPZs and be protected against

LEMP by relevant Surge Protection Measures (SPM as defined

in BS EN 62305).

SPM were previously referred to as a LEMP Protection

Measures System (LPMS) in IEC/BS EN 62305:2006.

Figure 4 highlights the LPZ concept as applied to the

structure and to SPM. The concept is expanded upon in

IEC/BS EN 62305-3 and IEC/BS EN 62305-4.

Selection of the most suitable SPM is made using the risk

assessment in accordance with IEC/BS EN 62305-2.

Arandela de estanqueidad integrada: ajuste

garantizado, no puede perderse ni montarse

incorrectamente. Sin montaje

Figure 4. The LPZ concept

LPZ

0

Direct flash, full lightning current,

full magnetic field

Earth termination network

Rolling sphere

radius

Air termination

network

SPD

0

/1

Equipotential

bonding by means

of SPD

SPD

0

/1

Down conductor network

LPZ

0

No direct flash, partial

lightning or induced current,

full magnetic field

LPZ 1

No direct flash, partial

lightning or induced

current, damped

magnetic field

LPZ 2

No direct flash,

induced currents,

further damped

magnetic field

LPZ 3