3/13
Analog inputs (continued)
Analog outputs
High level inputs with
common point
High level inputs isolated
between channels
High level input with
common point
Outputs isolated between
channels
Outputs with common point
Voltage/current
Voltage/current
± 10 V, 0…10 V, 0…5 V, 1…5 V
± 10 V
0…20
mA, 4…20 mA
0…20
mA, 4…20 mA
–
16
channels
8
channels
4
channels
8
channels
Between channels:
common point
Between bus and channels:
1000
V
a
rms
Between channels and earth:
1000
V
a
rms
Between channels:
± 200 V
c
Between bus and channels:
1000
V
a
rms
Between channels and earth:
1000
V
a
rms.
Between channels:
common point
Between bus and channels:
1000
V
a
rms
Between channels and earth:
1000
V
a
rms
Between channels:
1500
V
a
rms
Between bus and channels:
1500
V
a
rms
Between channels and earth:
1500
V
a
rms
Between channels:
common point
Between bus and channels:
1000
V
a
rms
Between channels and earth:
1000
V
a
rms
51
ms (normal scan)
3
ms/channel used
(
fast scan)
126.4
ms (normal scan)
3.3
ms/channel used
(
fast scan)
1
ms
–
–
User-definable filtering
0…6.50
s
User-definable filtering
0…3.82
s
–
2.5
ms
5
ms
12
bits
16
bits
11
bits + sign
13
bits + sign for voltage
13
bits for current
Two 25-way SUB-D
connectors
One 25-way SUB-D
connector
One 25-way SUB-D
connector
20-
way screw terminal
blocks: TSX BLY 01
One 25-way SUB-D
connector
or two Modicon Telefast
ABE 7CPA02/03 sub-bases
or one Modicon Telefast
ABE 7CPA02/31 sub-base
or one Modicon Telefast
ABE 7CPA03/21 sub-base
or one Modicon Telefast
ABE 7CPA02/03 sub-base
PLC: IEC/EN 61131-2
See page 9/6
TSX AEY 1600
TSX AEY 810
TSX AEY 420
TSX ASY 410
TSX ASY 800
3/16
2
1
3
4
5
6
7
8
9
10