11/50

Dimensions

Section 12

11

400 Hz network

Technical advice

Compatibility of 50/60 Hz equipment with a 400 Hz

network

The performance of products designed for domestic frequencies of 50/60 Hz is

impacted by the specific properties of networks of 400 Hz frequency.

Phenomena due to the increased frequency influence the behaviour of the copper

components of transformers, cables and protective equipment.

Some types of equipment designed for 50/60 Hz networks may not be suitable.

You should check whether or not a product is compatible and also apply any

correction factors given by the manufacturer.

Circuit breakers

Depending on the technologies used, modular circuit breakers designed for

50/60 Hz can be used at 400 Hz.

To choose the performance of a modular circuit breaker:

b

b

do not take any thermal derating into account

(In at 400 Hz is equivalent to In at 50 Hz).

b

b

increase the magnetic tripping threshold, according to the table below.

b

b

check that the short-circuit current on the installation is less than the breaking

capacity of the circuit breaker. The breaking capacity of the circuit breakers at a

frequency of 400 Hz is the same as at frequencies of 50/60 Hz. This characteristic

is generally complied with, due to the fact that the short-circuit current of a 400

Hz generator is relatively low. In most cases, the generator Isc does not exceed

four times the rated current.

Circuit breaker

Curve

Magnetic trip thresholds

50 Hz

400 Hz

Tolerance

iDPN

B

4 In

6 In

± 20 %

C

8 In

12 In

D

12 In

18 In

iC60

B

4 In

5.6 In

C

8 In

11.2 In

D

12 In

16.8 In

C60

B

4 In

5.1 In

C

8.5 In

10.9 In

D

12 In

15.4 In

C120

The NG125 and C120 circuit breakers are not suitable for networks of

400 Hz frequency. Refer to the Compact NSX offer.

NG125