11/53

Dimensions

Section 12

11

In

θ

I

t

1st peak

10 to 25 In

Transformers

High inrush currents are also produced when transformers are switched on,

typically 10 - 15 times full load current.

Assumptions

The tables give recommended MCB ratings for single phase transformers up to

12500VA and three phase transformers up to 30000VA based on the following

formula.

Inrush currents

When LV/LV transformers are switched on, very high inrush currents are produced

which must be taken into account when choosing overcurrent protection devices.

The peak value of the first current wave often reaches 10 - 15 times the rated rms

current of the transformer and may reach values of 20 - 25 times the rated current

even for transformers rated less than 50kVA. This transient inrush current decays

very quickly (in a few milliseconds).

Table 3 - 3 phase transformers 415Vac supply

VA Primary In (A)

C60HB

C60HC

C60HD

500 0.7

4

2

1

750 1.04

6

4

2

1000 1.39

10

6

4

2000 2.78

16

10

6

5000 6.95

40

25

16

10000 13.89

-

50

25

15000 20.84

-

63

32

20000 27.78

-

-

50

25000 34.73

-

-

63

30000 41.67

-

-

63

Table 4 - 1 phase transformers 240Vac supply

VA Primary In (A)

C60HB

C60HC

C60HD

50

0.21

2

-

-

100 0.42

4

2

1

250 1.04

6

4

2

500 2.08

16

10

4

1000 4.17

25

16

10

2500 10.42

63

32

16

5000 20.84

-

63

32

10000 41.66

-

-

63

12500 52.08

-

-

-

For use in conjunction with

motor starters and transformers (cont.)

Miniature circuit

breakers