Section 12

11

Safepact 2

Motor

loads

Discrimination

The table below indicates where total discrimination exists between devices.

D1

D2

Note:

n

These tables offer guidance only, for DOL starting assuming:

A starting current of 7 x FLC

Run-up time =8 seconds for motors

< 3kW

10 seconds for motors

> 3kW

n

The running current is a typical value and may vary from manufacturer to

manufacturer

Upstream Compact

MGE1003X MGE1253X MGE1603X MGE2003X MGE2503X MGE4003X MGE6303X

Downstream

circuit breaker

Rating (A)

multi 9

iC60H

10 - 16

n

n

n

n

n

n

n

20 - 25

n

n

n

n

n

n

32 - 40

n

n

n

n

n

n

50 - 63

n

n

n

n

n

n

Note:

For further information on this product range: consult us.

Guidance for motor loads

Specific “magnetic only” MCCBs are available for short circuit protection of motors.

However, the standard MCCB may be used, as detailed below.

Max motor size (kW)

Running current

(A) @ 415V

16A

2.2

5.0

25A

3.7

7.5

40A

4

8.4

63A

9

17

80A

15

28

100A

22

40

125A

25

47

160A

33

60

200A

45

80

250A

69

128