Section 12

11

Auxiliaries:

n

Alarm switch.

n

ON/OFF switch.

n

Shunt trip release or undervoltage release

(emergency stop).

Single phase connection

Emergency switch wiring

Time/current characteristics

Two poles of

the apparatus

must be

connected in

series for the

single phase

supply

The early

closing of

the auxiliary

contact is

necessary to

enable the

closing of the

circuit breaker

equipped with

an undervoltage

release

20

10

5

2

1

40

20

10

5

2

1

200

50

20

5

2

1.5

x rated current

2 3 4 6 8 10 15 20 30

Minutes

Seconds

Milliseconds

U

Ph

L1 L2 L3

3 5

N

1

2 4 6

Rating

In (A)

Settings

Part number

Standard power ratings kW:

of 3-phase motors 50 - 60Hz AC-3 category

230

400

415

440

500

690

0.16 0.1 - 0.16

21100

-

-

-

-

-

-

0.25 0.16 - 0.25

21101

-

-

-

-

-

-

0.40 0.25 - 0.40

21102

-

-

-

-

-

-

0.63 0.40 - 0.63

21103

-

-

-

-

-

0.37

1.0

0.63 - 1

21104

-

-

-

0.37

0.37

0.55

1.6

1 - 1.6

21105

-

0.37

-

0.55

0.75

1.1

2.5

1.6 - 2.5

21106

0.37

0.75

1.1

1.1

1.1

1.5

4.0

2.5 - 4

21107

0.75

1.5

1.5

1.5

2.2

3

6.3

4 - 6.3

21108

1.1

2.2

2.2

3

3.7

4

10

6 - 10

21109

2.2

4

4

4

5.5

7.5

14

9 - 14

21110

3

5.5

5.5

7.5

9

11

18

13 - 18

21111

4

7.5

9

9

10

15

23

17 - 23

21112

5.5

9

11

11

11

18.5

25

20 - 25

21113

5.5

11

11

11

15

22

P25M circuit breakers (cont.)

Motor

protection