11/52

Dimensions

Section 12

11

Motor starters

In general miniature circuit breakers can give only short circuit protection to motor

loads due to the high starting currents which may be encountered; typically 3 - 12

times full load current (FLC).

Assumptions

The tables give recommended MCB ratings for motors up to 37kW based on the

following assumptions:

n

Direct-on-line starting

Starting current = 7 x FLC

Run up time = 6seconds, motors <3kW

10 seconds, motors < 22kW

Running currents = average values only (individual manufacturer’s figures will

vary). four pole motors, i.e. speed approx. 1500rpm

For higher inertia loads, i.e. hoists or fans, run up times may be considerably

longer than those assumed above. The rating of the MCB must take account

of the greater run up time and starting current. The required MCB rating can be

determined by reference to time/current curves (consult us).

n

Star/delta starting

Since, during the changeover from star to delta, a high current surge in the order

of DOL values may be met, the MCB rating selected should be the same as that

recommended for DOL starting.

Table 1 - 3 phase 415Vac D.O.L. starting

Recommended MCB

kW hHp Running I

C60HB

C60HC

C60HD

0.12 0.166 0.65

2

2

1

0.18 0.25 0.7

2

2

1

0.25 0.33 0.87

4

2

1

0.37 0.5 1.35

4

4

2

0.55 0.75 1.55

4

4

2

0.75 1.0 1.93

6

4

4

1.1 1.5 2.5

6

6

4

1.5 2

3.5

10

10

6

2.2 3

4.8

16

10

10

3

4

6.4

20

20

10

3.75 5

7.8

25

25

16

4

5.5 8.1

25

25

16

5.5 7.5 11

32

32

16

7.5 10

14.4

50

50

20

9.33 12.5 17.3

63

50

20

11 15

21

63

63

25

13 17.5 25

-

-

32

15 20

28

-

-

40

18.5 25

35

-

-

50

22 30

40

-

-

50

30 40

54

-

-

63

37 50

65.5

-

-

-

Table 2 - 1 phase 240Vac D.O.L. starting

kW Hp Running I

C60HB

C60HC

C60HD

0.12 0.166 0.95

4

2

1

0.18 0.25 1.5

4

4

2

0.25 0.33 1.7

6

4

2

0.37 0.5 3

10

6

4

0.55 0.75 4.5

16

10

6

0.75 1

5.5

16

16

10

1.1 1.5 8.5

25

25

16

1.5 2

10.5

32

32

20

2.2 3

15.5

40

40

25

3

4

20

63

63

32

3.75 5

24

-

63

40

5.5 7.5 34

-

-

50

6.3 8.5 36.5

-

-

63

7.5 10

45

-

-

63

11 15

66.5

-

-

-

For use in conjunction with

motor starters and transformers

Miniature circuit