11/47
Dimensions
Section 12
11
Circuit breakers for direct
current applications (cont.)
24 V - 48 V direct current applications
Technical advice
24 V DC generator power supply protection
b
b
Earthed network:
v
v
Isc = 10 kA / In = 63 A,
v
v
Isc = 10 kA / In = 20 A.
Solution
iC60H 2P 63 A + iC60N 2P 20 A + DC loads
DB124262
In
1
In
2
Isc
1
AC network
Load 1
Isc
2
DC network
Load 2
Load 3