Dimensions

Section 12

11

Circuit breakers for direct

current applications (cont.)

24 V - 48 V direct current applications

Technical advice

Personal protection

Personal protection (earth-leakage protection) is not mandatory for this voltage

range (24-48 V DC).

In fact, according to the standards currently in force, the minimum ventricular

fibrillation current

If

for human beings is in the order of 25 mA for alternating current

(50 Hz), whereas for direct current, it is more than 50 mA.

The table below shows the data according to the standards and conditions:

Environment

Voltage specifications

AC

DC

Dry environment

Zman = 2000 Ohm

Uf = Z x If 50 V

100 V

Wet environment

Zman = 1000 Ohm

Uf = Z x If 25 V

50 V

With

Z

corresponding to the impedance of the human body in the different types of

environment,

If

being the current passing through the body and

Uf

the minimum contact voltage

required to reach the danger current.

Under normal operating conditions, this voltage range (< 50 V) is therefore not

dangerous to human beings.

DB124238

DB124239

DB124237

U

f

I

f

Z

man

Standards: IEC 60479-2, NF C 15100, IEC 60755.