Automatic lighting management in areas that benefit from natural light : e.g. individual and open-plan offices, meeting rooms

Presence mode : automatic on/off switching upon detection

Absence mode : manual switching on with push button, automatic switching off

Factory pre-set : time delay 15 minutes, light level threshold 500 lux for false ceiling sensors, 300 lux for flush mounted sensors

Pack

Cat. Nos.

360° ceiling sensors (indoor)

Fixed directly to a false ceiling with mounting claws

(supplied) or installed in 50 mm deep flush mounting

box or in surface mounting box Cat. Nos. 0488 74/75,

see p. 83

Detection field 45 m² - for private offices

PIR - Ø8 m - IP 20

Optimum distance between 2 sensors : 6 m

Consumption 0 . 4 W on standby

Absence and presence mode (push button override

or mobile configurator)

1

0488 07 Automatic terminal connection

All loads 8 . 5 A - 240 V

1

0488 08 Fast connection

All loads 8 . 5 A - 240 V

Detection field 90 m² - for meeting rooms

or large offices

Dual-tech - Ø11 m - IP 20

Optimum distance between 2 sensors : 10 m

Consumption 0 . 8 W on standby

Absence and presence mode (push button override

or mobile configurator)

1

0488 06 Automatic terminal connection

All loads 8 . 5 A - 240 V

1

0488 09 Fast connection

All loads 8 . 5 A - 240 V

Detection field 45 m² - for enclosed spaces with

obstacles

Ultrasonic - Ø8 m - IP 20

Optimum distance between 2 sensors : 6 m

Consumption 0 . 8 W on standby

Absence and presence mode (push button override

or mobile configurator)

1

0488 05 Automatic terminal connection

All loads 8 . 5 A - 240 V

Detection field 90 m²- for corridors or very long

areas

PIR - 30 m² - IP 20

Optimum distance between 2 sensors : 20 m

Consumption 0 . 4 W on standby

Absence and presence mode (push button override

or mobile configurator)

1

0488 17 Automatic terminal connection

All loads 8 . 5 A - 240 V

Pack

Cat. Nos.

180° wall sensor (indoor)

For warehouses, corridors or very long areas

PIR -Maximum range 30 m - IP 42

Consumption 0 . 4 W on standby

Detection specially adapted for long narrow areas

(e.g. corridors) or very high areas (e.g. warehouses)

Presence mode

1

0488 13 Automatic terminal connection

All loads 2 . 5 A - 240 V

270° wall sensor (outdoor)

Detection field 180 m² - for building entrances,

car parks

PIR - Maximum range 15 m - IP 55

Front detection 10 m

Lateral detection 30 m (2 x 15)

IP 55

Consumption 0 . 4 W on standby

Dual side detection specially adapted for wide areas

(e.g. entrance hall)

Absence and presence mode (push button override

or mobile configurator)

1

0488 10 Automatic terminal connection

All loads 8 . 5 A - 240 V

180° switch sensors (indoor)

Detection field 15 m² - for small conference

rooms and private offices

Wall mounting

Absence mode with neutral

Dual-tech - Maximum range 8 m - IP 41

Arteor

1

5740 49 White

1

5740 99 Magnesium

Absence mode without neutral

PIR - Maximum range 8 m - IP 41

Arteor

1

5740 31 White

1

5740 81 Magnesium

0488 07

5740 49

0488 13

0488 17

Main characteristics and applications selection charts p. 78-79 Technical characteristics p. 84-85

lighting management

standalone sensors - 1 output

for areas benefitting from natural light

NEW

NEW

NEW

NEW