Cat. Nos.
With/
without
neutral
Power
supply
TYPE OF LIGHT COMPATIBILITY
ON/OFF
Dimming
Contactors
Halogen
light
ELV halogen
with separate
ferromagnetic or
electromagnetic
transformer
Fluorescent
tube
Fluorescent light
with separate
ferromagnetic or
electronic ballast
LED
Compact
fluorescent light
with 1-10 V
ballasts
DALI
ballast
1 OUTPUT
0488 03
With
neutral
240 V 2 000 W 1 000 VA 10 x (2 x 36 W)
1 000 VA
500 W 500 W
–
max.
≤
2 A
100 V 1 000 W 1 500 VA 5 x (2 x 36 W)
500 VA
250 W 250 W
max.
≤
2 A
0488 11
With
neutral
240 V 2 000 W 1 000 VA 10 x (2 x 36 W)
1 000 VA
500 W 500 W
–
max.
≤
2 A
100 V 1 000 W 1 500 VA 5 x (2 x 36 W)
500 VA
250 W 250 W
max.
≤
2 A
0697 40
0697 80
With
neutral
240 V 2 000 W 1 000 VA 10 x (2 x 36 W)
1 000 VA
500 W 500 W
–
max.
≤
2 A
100 V 1 000 W 1 500 VA 5 x (2 x 36 W)
500 VA
250 W 250 W
max.
≤
2 A
5740 47
5740 97
With
neutral
240 V 2 000 W 1 000 VA 10 x (2 x 36 W)
1 000 VA
500 W 500 VA
–
max.
≤
2 A
100 V 1 000 W 500 VA
5 x (2 x 36 W)
500 VA
250 W 250 VA
max.
≤
2 A
5740 34
5740 94
Without
neutral
240 V 400 W max
40 W min
400 VA
40 VA
–
–
–
–
–
–
100 V 200 W max
20 W min
200 VA
20 VA
0488 05
With
neutral
240 V 2 000 W 1 000 VA 10 x (2 x 36 W)
1 000 VA
500 W 500 W
–
max.
≤
2 A
100 V 1 000 W 1 500 VA 5 x (2 x 36 W)
500 VA
250 W 250 W
max.
≤
2 A
0488 06
0488 09
With
neutral
240 V 2 000 W 1 000 VA 10 x (2 x 36 W)
1 000 VA
500 W 500 W
–
max.
≤
2 A
100 V 1 000 W 1 500 VA 5 x (2 x 36 W)
500 VA
250 W 250 W
max.
≤
2 A
0488 07
0488 08
With
neutral
240 V 2 000 W 1 000 VA 10 x (2 x 36 W)
1 000 VA
500 W 500 W
–
max.
≤
2 A
100 V 1 000 W 1 500 VA 5 x (2 x 36 W)
500 VA
250 W 250 W
max.
≤
2 A
0488 17
With
neutral
240 V 2 000 W 1 000 VA 10 x (2 x 36 W)
1 000 VA
500 W 500 W
–
max.
≤
2 A
0488 10
With
neutral
240 V 2 000 W 1 000 VA 10 x (2 x 36 W)
1 000 VA
500 W 500 W
–
max.
≤
2 A
100 V 1 000 W 1 500 VA 5 x (2 x 36 W)
500 VA
250 W 250 W
max.
≤
2 A
0488 13
With
neutral
240 V 2 000 W 1 000 VA 10 x (2 x 36 W)
1 000 VA
500 W 500 W
–
max.
≤
2 A
100 V 1 000 W 1 500 VA 5 x (2 x 36 W)
500 VA
250 W 250 W
max.
≤
2 A
5740 49/
5740 99
With
neutral
240 V 2 000 W 1 000 VA 10 x (2 x 36 W)
1 000 VA
500 W 500 VA
–
max.
≤
2 A
100 V 1 000 W 500 VA
5 x (2 x 36 W)
500 VA
250 W 250 VA
max.
≤
2 A
5740 31
5740 81
Without
neutral
240 V 400 W max
40 W min
400 VA
40 VA
–
–
–
–
–
–
100 V 200 W max
20 W min
200 VA
20 VA
2 OUTPUTS
0488 50
(1)
With
neutral
240 V 3 600 W 1 800 VA
1 800 VA
500 W 500 W 1 800 VA
–
max.
≤
2 A
100 V 1 800 W 900 VA
900 VA
250 W 250 W 900 VA
0488 51
With
neutral
240 V
–
–
–
–
–
–
2 x 16
ballasts max.
≤
2 A
100 V
0488 52
With
neutral
240 V
–
–
–
–
–
1000 VA
–
–
100 V
–
–
–
–
–
500 VA
lighting management
standalone sensors
main characteristics and applications
79