Table of Contents Table of Contents
Previous Page  107 / 320 Next Page
Information
Show Menu
Previous Page 107 / 320 Next Page
Page Background

1.92

Data is subject to errors and technical modifications.

Surge Protection Devices

Type 3 / Class III, SP202N

Commercial

Distribution

Characteristics

Tested to

EN 61643-11 (VDE0675-6-11) 2007-08

SPD type / class

Type 3 / III

Ports

one port

Type of connection

Parallel connection

Type of power supply system

TT / TN system

Nominal voltage

U N

230V ac

Rated voltage

U c

255V ac

Voltage protection level ( L- N)

U p

≤ 1.25kV

Voltage protection level

(L/N - PE)

U p

≤ 1.5kV

TOV - Characteristic (L - N)

UT

335V / 5s

TOV - Characteristic (L/N - PE) (I)

UT

400V / 5s

TOV - Characteristic (L/N - PE) (II)

UT

1200V / 200 ms

Rated load current

IL

16 Aeff

Nominal discharge current (8/20)

I n

3kA

Maximal discharge current (8/20)

I max

5kA

Combination wave (1,2/50 - 8/20) (L - N)

U oc

6 kV

Combination wave (1,2/50 - 8/20) (L/N - PE)

U oc

10 kV

Residual current

IPE

≤ 5μA

Remplacement cartridge

NO

Maximal rating of overcurrent protection

fuse

16 A gL / gG

MCB 16A B curve

Short-circuit withstand capability with max. overcur-

rent protection

fuse

6kA eff ac

MCB 1kA eff ac

Response time

t A

≤ 25ns

Operating temperature range

- 25°C ….+ 40°C

Indication of SPD disconnector

NO

Remote signalisation contact

Green light off

Cross sectional area

min

1.5mm

2

solid / flexible

max

10mm

2

stranded / 6mm

2

flexible

Tightening torque for terminals

1.2 Nm

Mounting on

35mm DIN rail in accordance with EN 60715

Enclosure material

Grey thermoplastic, UL 94V-2

Degree of protection

IP20

Installation width

2 modules, DIN 43880

Reserve Indicator Light

Neutral cartridges cannot be put into

spares reserved for phase cartridges and

visa versa.

Normal

Reserve

End of Life