Table of Contents Table of Contents
Previous Page  111 / 320 Next Page
Information
Show Menu
Previous Page 111 / 320 Next Page
Page Background

1.96

Data is subject to errors and technical modifications.

MCCBs

Technical Data

Commercial

Distribution

Frame

x160

x250

Product

MCS Switch MCCB

MCS Switch MCCB

Reference

HCA

HDA

HHA

HNA

HCB

HHB

HNB

Number of poles

[No.] 3-4

1-2-3-4

1-2-3-4

3-4

3-4

Electrical characteristics

Rated current

I n

[A]

160

250

Current rated range

[A]

125-160

16-125 (1P), 16-160 (2, 3, 4P)

250

100-250

Rated service voltage, (AC)

U e [V]

220-440

220-440

Frequency

F [Hz] 50/60

50/60

Rated insulation voltage

U i

[V]

690

800

Rated impulse withstand voltage

U imp [kV] 8

8

Rated ultimate short-circuit breaking capacity, (I cu )

(AC) 50-60 Hz 220/230 V

I cu [kA]

-

25

35

85

-

35

85

(AC) 50-60 Hz 380/415 V

I cu [kA] -

18

25

40

-

25

40

(AC) 50-60 Hz 480/500/525 V I cu [kA] -

6

7.5

12.5

-

-

10

(AC) 50-60 Hz 660/690 V

I cu [kA] -

-

-

6

-

-

4

(DC) 250 V - 2 poles in series I cu [kA] -

12.5

20

25

-

25

25

Rated service short-circuit breaking capacity, (I cs )

(AC) 50-60 Hz 220/230 V

I cs [kA]

-

25

25

40

-

25

40

(AC) 50-60 Hz 380/415 V

I cs [kA] -

18

20

20

-

20

20

(AC) 50-60 Hz 480/500/525 V I cs [kA] -

3

4

7.5

-

7.5

(AC) 50-60 Hz 660/690 V

I cs [kA] -

-

-

3

-

-

2

(DC) 250 V - 2 poles in series I cs [kA] -

7

10

13

-

13

13

Rated short-circuit making capacity

I cm [kA] 2.8

-

-

-

6

-

-

Rated short-time withstand current for 1s I cw [kA] 2

-

-

-

3

-

-

Category of use (EN 60947-2)

-

A

-

A

Calibration temperature

-

50°C

-

50°C

Derating 40°C

-

100%

-

100%

50°C

-

100%

-

100%

55°C

-

95%

-

94%

60°C

-

93%

-

91%

65°C

-

90%

-

88%

Suitability for isolation

ok

ok

Electric endurance in number of cycles

10000

10000

Mechanical endurance in number of operations

20000

20000

Operating temperature

-25 to +70°C

-25 to +70°C

Storage temperature

-35 to +70°C

-35 to +70°C

Power loss (at I n for 3P)

[W] 39

60

Reference standard

IEC 60947-3

IEC 60947-2

IEC 60947-3

IEC 60947-2

Releases: switch

ok

-

ok

-

Releases: TM (thermomagnetic)

-

ok

-

ok

T fixed, M fixed

-

ok (1P)

-

ok

T adjustable, M fixed

-

ok

-

-

T adjustable, M adjustable

-

-

-

ok

Thermal adjustment value

-

0.63 to 1 x I n

-

0.63 to 1 x I n

Magnetic adjustment value

-

-

-

6-8-10-13 x I n (200A)

5-7-9-11 I n (250A)

Releases: LSI (electronic)

-

-

-

-

Long delay

-

-

-

-

Short delay

-

-

-

-

Time delay

-

-

-

-

Terminations

Standard terminal type

cage

lugs

Maximum terminal capacity

95 mm

2

185 mm

2

(cage)

Terminal width

mm -

25

Terminal shields

ok

ok

Cage terminal

integrated

ok

Extended connections

ok

ok

Rear connections

no

ok

Dimensions

Height

mm 130

165

Width

1P mm -

25

-

-

2P mm -

50

-

-

3P mm 75

105

4P mm 100

140

Depth

mm 68

68

Weight

1P kg -

0.29

-

-

2P kg -

0.48

-

-

3P kg 0.715

1.3

4P kg 0.95

1.6