Table of Contents Table of Contents
Previous Page  113 / 320 Next Page
Information
Show Menu
Previous Page 113 / 320 Next Page
Page Background

1.98

Data is subject to errors and technical modifications.

MCCBs

x160 Technical Data

Commercial

Distribution

MCCBs

Thermal settings

220/240V AC

IEC 60 947-2

380/415V AC

IEC 60 947-2

HDA

I cu 25 kA

18 kA

I cs 25 kA

18 kA

HHA

I cu 35 kA

25 kA

I cs 25 kA

20 kA

HCA

I cm -

2.8 kA

I cw -

2 kA - 1s

Thermal adjustment from 0.63 to 1 x I n

1

3

I n

16 - 50 A 63 - 80 A 100 - 125 A 160 A

I mag

600 A

1000 A

1500 A

1600 A

Magnetic adjustment fixed > 10 x I n

For DIN rail mounting, use

HYA033H

.

Ech. 30%

PUSH TO TRIP

PUSHTOTRIP

Ech. 65%

TRIP

Ir

(x In)

2

6