Table of Contents Table of Contents
Previous Page  105 / 320 Next Page
Information
Show Menu
Previous Page 105 / 320 Next Page
Page Background

1.90

Data is subject to errors and technical modifications.

Surge Protection Devices

Type 1 + Type 2, SPA215*, SPA400*, SPA401*

Commercial

Distribution

SPA201

SPA401

Tested to

EN 61643-11 2002-12

SPD type / class

Type 1 + Type 2 / Class I

Energy-coordinated protection

effect on terminal equipment

Type 1 + Type 2

Energy-coordinated protection

effect on terminalequipment

≤ 5 m

Type 1 + Type 2 + Type 3

Type of connection

Parallel connection

Type of power supply system

TT / TN system

Type of protection

common and differential modes

Nominal voltage

U N 230V/400V ac

Rated voltage

U c

255V ac

Voltage protection level

U p

≤ 1.5kV

TOV Voltage

U T

440V / 5s

1200V / 200ms

Rated load current

I(L)

n/a

I(L-L)

n/a

Follow current interrupting rating I fi

25kA rms

100A rms

Nominal discharge current (8/20) I n

12.5kA

25kA

12.5kA

50kA

Impulse current (10/350)

I imp 12.5kA

25kA

12.5kA

50kA

Max. rating of overcurrent

protection

fuse 160A gL / gG

MCCB n/a

160A

Short-circuit withstand

capability with max. overcurrent

protection

fuse 25kA rms

MCB n/a

Response time

t A

≤ 100ns

Operating temperature range

- 40°C ….+ 80°C

Indication of SPD disconnector

Green/Red flag on L and N

Green/Red flag on L1, L2, L3 and N

Cross sectional area

min

1,5mm

2

solid / flexible

max 35mm

2

stranded / 25mm

2

flexible

Tightening torque for terminals

4 Nm

Mounting on

35mm DIN rail in accordance with EN 60715

Enclosure material

grey thermoplastic, UL 94V-0

Degree of protection

IP20

Modular width

2

4

Weight

275 g

480 g

Approval marking

KEMA