Table of Contents Table of Contents
Previous Page  104 / 320 Next Page
Information
Show Menu
Previous Page 104 / 320 Next Page
Page Background

1.89

Data is subject to errors and technical modifications.

Surge Protection Devices

Type 1 + Type 2 / Class I, SPN8***

Commercial

Distribution

SPN801 / SPN801R

SPN802 / SPN802R

Tested to

EN 61643-11

(VDE0675-6-11) 2002-12

EN 61643-11

(VDE0675-6-11) 2002-12

L1/L2/L3/N => PE

L1/L2/L3 => N

N => PE

SPD type / class

Type 1 + Type 2 / I / B

Type of connection

Parallel connection

Type of power supply system

TN-S - System

TT

- System

Type of protection

Common modes

Common and differential modes

Nominal voltage

U N 230V / 400V ac

Rated voltage

U c

255V ac

Voltage protection level

U p

≤ 1.5kV

255V ac

TOV-voltage

U T

440V / 5s

1200V / 200ms

Rated load current

I(L)

315A

I(L-L)

125A

Follow current interrupting rating

I fi

50 kA

100kA

Nominal discharge current (8/20)

I n

100kA

25kA

100kA

Impulse current (10/350)

I imp 100kA

25kA

100kA

Residual current

I PE

≤ 100mA

Max. rating of overcurrent protection fuse

125A gL / gG serial or 315A parallel

MCCB 125A serial or 160A parallel

Short-circuit withstand capability with

max. overcurrent protection

fuse

50kA ac

25kA ac

MCCB 50kA ac

25kA ac

Response time

t A

< 100ns

Operating temperature range

- 40°C ….+ 60°C

Indication of SPD disconnector

Green - red on L1, L2, L3, N

Cross sectional area

min

10mm

2

solid / flexible

L1, L2, L3, PE

max

50mm

2

multi-stranded / 35mm

2

flexible

Tightening torque for terminals

7.0 Nm

Mounting on

35mm DIN rail in accordance with EN 60715

Enclosure material

grey thermoplastic, UL 94V-0

Degree of protection

IP20

Modular width

6

8

Weight

1260 g

1272 g

Approval marking

VDE