1.89
Data is subject to errors and technical modifications.
Surge Protection Devices
Type 1 + Type 2 / Class I, SPN8***
Commercial
Distribution
SPN801 / SPN801R
SPN802 / SPN802R
Tested to
EN 61643-11
(VDE0675-6-11) 2002-12
EN 61643-11
(VDE0675-6-11) 2002-12
L1/L2/L3/N => PE
L1/L2/L3 => N
N => PE
SPD type / class
Type 1 + Type 2 / I / B
Type of connection
Parallel connection
Type of power supply system
TN-S - System
TT
- System
Type of protection
Common modes
Common and differential modes
Nominal voltage
U N 230V / 400V ac
Rated voltage
U c
255V ac
Voltage protection level
U p
≤ 1.5kV
255V ac
TOV-voltage
U T
440V / 5s
1200V / 200ms
Rated load current
I(L)
315A
I(L-L)
125A
Follow current interrupting rating
I fi
50 kA
100kA
Nominal discharge current (8/20)
I n
100kA
25kA
100kA
Impulse current (10/350)
I imp 100kA
25kA
100kA
Residual current
I PE
≤ 100mA
Max. rating of overcurrent protection fuse
125A gL / gG serial or 315A parallel
MCCB 125A serial or 160A parallel
Short-circuit withstand capability with
max. overcurrent protection
fuse
50kA ac
25kA ac
MCCB 50kA ac
25kA ac
Response time
t A
< 100ns
Operating temperature range
- 40°C ….+ 60°C
Indication of SPD disconnector
Green - red on L1, L2, L3, N
Cross sectional area
min
10mm
2
solid / flexible
L1, L2, L3, PE
max
50mm
2
multi-stranded / 35mm
2
flexible
Tightening torque for terminals
7.0 Nm
Mounting on
35mm DIN rail in accordance with EN 60715
Enclosure material
grey thermoplastic, UL 94V-0
Degree of protection
IP20
Modular width
6
8
Weight
1260 g
1272 g
Approval marking
VDE