Table of Contents Table of Contents
Previous Page  99 / 320 Next Page
Information
Show Menu
Previous Page 99 / 320 Next Page
Page Background

1.84

Data is subject to errors and technical modifications.

Miniature Circuit Breakers

Zs Values

Commercial

Distribution

Max Let-Through Energy (kA

2

s) at

PSCC

Max Z s (ohms)

I n

3kA

6kA

10kA

0.2 - 1s

sec

5 sec

MTN/NBN (B Curve)

6

5.9

10.5

15

7.28

7.28

10

6.5

12.2

21.5

4.37

4.37

16

8.0

17.5

30

2.73

2.73

20

8.8

19.5

34

2.19

2.19

25

10

21

38

1.75

1.75

32

11

24

42

1.37

1.37

40

12.5

29

50

1.09

1.09

50

15

34

61

0.87

0.87

63

16

38

72

0.69

0.69

NCN/HM (C Curve)

0.5

0.01

0.01

0.01

43.7

62.43

1

4.0

7.0

10

21.85

31.21

2

4.0

7.0

10

10.93

15.61

3

5.0

10.0

15

7.28

10.40

4

5.9

10.5

15

5.46

7.80

6

5.9

10.5

15

3.64

5.20

10

6.5

12.2

21.5

2.19

3.12

16

8.0

17.5

30

1.37

1.95

20

8.8

19.5

34

1.09

1.56

25

10

21

38

0.87

1.25

32

11

24

42

0.68

0.98

40

12.5

29

50

0.55

0.78

50

15

34

61

0.44

0.62

63

16

38

72

0.35

0.50

80

-

-

-

1.27

0.39

100

-

-

-

0.22

0.31

125

-

-

-

0.1

0.25

NDN (D Curve)

0.5

0.01

0.01

0.01

21.85

62.43

1

4.0

7.0

10

10.93

31.21

2

4.0

7.0

10

5.46

15.61

3

5.0

10.0

15

3.64

10.40

4

5.9

10.5

15

2.73

7.80

6

5.9

10.5

15

1.82

5.20

10

6.5

12.2

21.5

1.09

3.12

16

8.0

17.5

30

0.68

1.95

20

8.8

19.5

34

0.55

1.56

25

10

21

38

0.44

1.25

32

11

24

42

0.34

0.98

40

12.5

29

50

0.27

0.78

50

15

34

61

0.22

0.62

63

16

38

72

0.17

0.50

80

0.14

0.39

100

0.11

0.31

125

0.09

0.25

Earth Fault Loop impedance (Z s ) values for MCBs and MCCBs

Below are the maximum permissible values of Z s to obtain disconnection for

compliance with BS 7671:2008 Amendment 3