Transformers & Motors

Protection

Commercial

Distribution

Transformer Protection

Tables 19 & 20 show the recommended MCB’s for the protection of single

phase (230V) and three phase (400V) transformers.

Single Phase 230V

Recommended MCB

Transformer

Rating (VA)

Primary

Current

NBN

NCN

NDN

50

0.22

-

1

6

100

0.43

-

2

6

200

0.87

-

3

6

250

1.09

6

4

6

300

1.30

10

4

6

400

1.74

10

6

6

500

2.17

16

10

6

750

3.26

16

10

6

1000

4.35

25

16

10

2500

10.87

63

40

20

5000

21.74

-

63

32

7500

32.60

-

-

50

10000

43.48

-

-

63

Three Phase 400V

Recommended MCB

Transformer

Rating (VA)

Primary

Current

NBN

NCN

NDN

500

0.72

-

3

6

750

1.08

6

4

6

1000

1.44

10

6

6

2000

2.88

16

10

6

3000

4.33

25

16

10

4000

5.77

32

20

10

5000

7.21

40

25

16

7500

10.82

63

32

20

10000

14.43

-

50

25

15000

21.64

-

63

32

20000

28.86

-

-

50

25000

36.07

-

-

63

Motor Circuit Protection

Tables 28,29,30 and 31 give general recommendations for the selection of

circuit breakers and HRC fuses for the protection of motor power circuits and

are based on the assumptions shown in Table 28 for a cage motor running at

approximately 1400 Rev/Min.

Motor Rating

DOL Starting

Conditions

Assisted Start Conditions

Up to 0.75kW 5 x FLC for 6 secs

2.5 x FLC for 15 secs

1.1 to 7.5kW 6 x FLC for 10 secs

2.5 x FLC for 15 secs

11 to 75kW 7 x FLC for 10 secs

2.5 x FLC for 15 secs

90 to 160kW 6 x FLC for 15 secs

2.5 x FLC for 20 secs

1 Phase 230V DOL Starting

Recommended Circuit Breaker

kW hp

FLC A (A)

NBN

(A)

NCN

(A)

NDN

Fuse (A)

0.18

0.25

2.8

16

10

10

10

0.25

0.33

3.2

16

10

10

16

0.37

0.5

3.5

16

10

10

16

0.55

0.75

4.8

20

16

16

16

0.75

1.0

6.2

25

20

20

20

1.1

1.5

8.7

40

25

25

25

1.5

2.0

11.8

50

32

32

32

2.2

3.0

17.5

-

50

50

40

3.0

4.0

20

-

63

63

50

3.75

5.0

24

-

-

-

63

5.5

7.5

36

-

-

-

80

7.5

10

47

-

-

-

100

3 Phase 400V Assisted Starting Star-Delta

Recommended Circuit Breaker

kW hp

FLC A (A)

NCN

(A)

NDN

HRC Fuse (A)

3

4

6.3

16

10

16

4

5.5

8.2

20

10

16

5.5

7.5

11.2

32

16

20

7.5

10

14.4

40

25

25

11

15

21

50

32

32

15

20

27

-

40

35

18.5

25

32

-

50

40

22

30

38

-

63

50

30

40

51

-

-

63

37

50

63

-

-

80

45

60

76

-

-

80

55

75

91

-

-

100

75

100

124

-

-

160

90

125

154

-

-

200

110

150

183

-

-

200

132

175

219

-

-

250

150

200

240

-

-

315

160

220

257

-

-

315