Low-Voltage Fuse Systems

3

NP LV HRC fuse switch disconnectors

3/68

Siemens ET B1 · 10/2008

3

*

You can order this quantity or a multiple thereof.

Selection and ordering data

All fuse switch disconnectors with flat terminals must be used

with the appropriate cable lug covers (3NY7 101 to 3NY7 141)

for finger-safe cover according to BGV A2,

see page 3/76

.

1)

See LV HRC Fuse Links.

2)

Insert silver-plated isolating links.

3)

125/160

A only possible with 21-mm wide 3NY1 822 (125 A) and 3NY1 824

(160

A) LV HRC fuse links,

see page 3/77

.

4)

Corresponds to LV HRC fuse link size 00 with maximum width 21 mm

(

according to IEC 60269-2-1 and DIN 43620).

5)

Can only be mounted on 5 mm thick busbars, a busbar thickness compensator

is required for 3NP42 and 3NP43;

see page 3/77

.

3

NP44 can only be mounted on busbars with a thickness of 10 mm!

Rated

residual

current

Connection type

(

double-ended)

For LV HRC

fuse links

acc. to

DIN 43620

1)

For

isolating

links

2)

Degree of protection IP00,

without fuse links,

without isolating links,

with terminal screws

I

u

Connection For

conductor

cross-section

DT Order No.

Price

per PU

PG PU PS*/

P. unit

Weight

per PU

approx.

A

mm

2

Size

Size

Unit(s) Unit(s) kg

Up to 160 A, also clip-on for standard mounting rail

160

3)

Box

terminals

1.5 ... 50 000

4)

00

}

3

NP40 10-0CH01

103 1

1

0.512

160

Flat

terminals

Up to 2

×

70 (

M8)

00

a. 000 00

}

3

NP40 70-0CA01

103 1

1

0.749

Box

terminals

2.5 ... 70

or

2

×

2.5 ... 16

}

3

NP40 70-0CH01

103 1

1

0.800

250

Flat

terminals

Up to 150

(

M10)

1

and 0 1 and 0

}

3

NP42 70-0CA01

103 1

1

2.436

400

Up to 240

(

M10)

2

and 1 2 and 1

}

3

NP43 70-0CA01

103 1

1

3.614

630

Up to 2

×

240 (

M12)

3

and 2 3 and 2

}

3

NP44 70-0CA01

103 1

1

4.984

For 40 mm busbar system

For busbars of width 12 mm or 15 mm and

thickness 5 mm or 10 mm

5)

With adapter, deep, e.g. for installation in ALPHA meter

cabinets (ALPHA 400-ZS) and ALPHA distribution boards

3

NP40 15-0CK01

160

3)

Box

terminals

1.5 ... 50

Connec-

tion, top

000

4)

00

A

3

NP40 15-0CK01

103 1

1

0.952

Connection,

bottom

A

3

NP40 15-0CJ01

103 1

1

0.970

160

Flat

terminals

Up to 2

×

70 (

M8)

Connec-

tion, top

00

a. 000 00

A

3

NP40 75-0CE01

103 1

1

1.210

Connection,

bottom

A

3

NP40 75-0CF01

103 1

1

1.244

Box

terminals

2.5 ... 70

or

2

×

2.5 ... 16

Connec-

tion, top

00

a. 000 00

A

3

NP40 75-0CK01

103 1

1

1.290

Connection,

bottom

A

3

NP40 75-0CJ01

103 1

1

1.274

© Siemens AG 2008