BETA Protecting

Low-Voltage Fuse Systems

3

NP LV HRC fuse switch disconnectors

3/66

Siemens ET B1 · 10/2008

3

*

You can order this quantity or a multiple thereof.

1)

Rated making and breaking current according to IEC 60947-3

rated making current

I

= 10 ×

I

e

(

AC-23); 3 ×

I

e

(

AC-22); 1.5 ×

I

e

(

AC-21)

rated breaking current

I

= 8 ×

I

e

(

AC-23); 3 ×

I

e

(

AC-22); 1.5 ×

I

e

(

AC-21).

2)

When electronic fuse monitors are used, infeed must be from the top.

3)

Insert silver-plated isolating links.

3

NP50

3

NP52

3

NP53

3

NP54

Short-circuit strength with fuses

(

with closed disconnector)

With fuse links

Rated current

Size/A

00/160

1/250

2/400

3/630

At 500 V AC

kA

(

r.m.s. value)

100

100

50

50

Maximum permissible let-through

I

2

t value

kA

2

s

223

780

2150

5400

Permissible let-through current of the fuses

kA

(

peak value)

23

32

40

60

Rated short-circuit making capacity

With isolating links

1)

Size

00

1

2

3

At 500 V AC

kA

(

peak value)

6

17

17

17

Rated making and breaking capacity

1)

(

infeed from top or bottom)

2)

Size

00

1

0

2

1

3

2

At 400 V AC, with fuse links

Breaking current

I

c

(

p.f. = 0.35)

A

(

r.m.s. value)

1600

2500 1600 4000 2500 5040 4000

Rated operational current

I

e

for

AC-21B, AC-22B, AC-23B

A

160

250

160

400

250

630

400

At 500 V AC, with fuse links

Breaking current

I

c

(

p.f. = 0.35)

A

(

r.m.s. value)

1300

2500 1600 4000 2500 5040 4000

Rated operational current

I

e

for

AC-21B, AC-22B, AC-23B

A

160

250

160

400

250

630

400

At 690 V AC, with fuse links

Breaking current

I

c

(

p.f. = 0.35)

A

(

r.m.s. value)

800

1280 1000 2520 1600 3200 2520

Rated operational current

I

e

at

AC-21B, AC-22B

A

160

250

160

400

250

630

400

AC-23B

A

100

160

125

315

200

400

315

At 220 (440) V DC, with 2 (3) conducting paths in

series and fuse links

Breaking current

I

c

(

L/R = 15 ms)

A

640

1000 640

1600 1600 2520 1600

Rated operational current

I

e

for DC-23B

A

160

250

160

250

250

630

400

Switching capacity with isolating links

3)

(

infeed from top or bottom)

At 400 V AC, with isolating links

Size

00

1

2

3

Breaking current

I

c

(

p.f. = 0.35)

A

(

r.m.s. value)

1600

2500

2500

4000

Rated operational current

I

e

at

AC-21B, AC-22B

A

160

250

400

630

AC-23B

A

160

250

315

500

At 500 V AC, with isolating links

Breaking current

I

c

(

p.f. = 0.35)

A

(

r.m.s. value)

1300

2500

2500

4000

Rated operational current

I

e

at

AC-21B, AC-22B

A

160

250

400

630

AC-23B

A

160

250

315

500

At 690 V AC, with isolating links

Breaking current

I

c

(

p.f. = 0.35)

A

(

r.m.s. value)

800

1280

1600

2520

Rated operational current

I

e

at

AC-21B, AC-22B

A

160

250

400

630

AC-23B

A

100

160

200

315

At 220 V DC, with isolating links

Breaking current

I

c

(

L/R = 15 ms)

A

640

1000

1600

1600

Rated operational current

I

e

for DC-23B

A

160

200

400

400

Switching capacity for horizontal installation

Up to 690 V AC-22B

No reduction of the specified switching capacity

(

values for AC-23B to 690 V on request)

© Siemens AG 2008