5/112

Contactors

Basic devices up to 170 A

2010

CA08103002Z-EN

www.eaton.com

DILM7

DILM9

DILM12

DILM15

DILM17

DILM25

AC voltage

AC-1 operation

Conventional free air

thermal current

3

pole

50 - 60

Hz

Open

at 40 °C

I

th

A

22

22

22

22

40

45

at 50 °C

I

th

A

21

21

21

21

38

43

at 55 °C

I

th

A

21

21

21

21

37

42

at 60 °C

I

th

A

20

20

20

20

35

40

Enclosed

I

th

A

18

18

18

18

32

36

Conventional free air

thermal current 1 pole

Open

I

th

A

50

50

50

50

88

100

Enclosed

I

th

A

45

45

45

45

80

90

AC-3 operation

Rated operational current

AC -3 open,

50 – 60

Hz, 3 pole

220/230

V

I

e

A

7

9

12

15.5

18

25

240

V

I

e

A

7

9

12

15.5

18

25

380/400

V

I

e

A

7

9

12

15.5

18

25

415

V

I

e

A

7

9

12

15.5

18

25

440

V

I

e

A

7

9

12

15.5

18

25

500

V

I

e

A

5

7

10

12.5

18

25

660/690

V

I

e

A

4

5

7

9

12

15

Rated operational power

220/230

V

P

kW 2.2

2.5

3.5

4

5

7.5

240

V

P

kW 2.2

3

4

4.6

5.5

8.5

380/400

V

P

kW 3

4

5.5

7.5

7.5

11

415

V

P

kW 4

5.5

7

8

10

14.5

440

V

P

kW 4.5

5.5

7.5

8.4

10.5

15.5

500

V

P

kW 3.5

4.5

7

7.5

12

17.5

660/690

V

P

kW 3.5

4.5

6.5

7

11

14

AC-4 operation

Rated operational current

AC-4 open,

50 - 60

Hz, 3 pole

220/230

V

I

e

A

5

6

7

7

10

13

240

V

I

e

A

5

6

7

7

10

13

380/400

V

I

e

A

5

6

7

7

10

13

415

V

I

e

A

5

6

7

7

10

13

440

V

I

e

A

5

6

7

7

10

13

500

V

I

e

A

4.5

5

6

6

10

13

660/690

V

I

e

A

4

4.5

5

5

8

10

Rated operational power

220/230

V

P

kW 1

1.5

2

2

2.5

3.5

240

V

P

kW 1.5

1.6

2.2

2.2

3

4

380/400

V

P

kW 2.2

2.5

3

3

4.5

6

415

V

P

kW 2.3

2.8

3.4

3.4

5

6.5

440

V

P

kW 2.4

3

3.6

3.6

5.5

7

500

V

P

kW 2.5

2.8

3.5

3.5

6

8

660/690

V

P

kW 2.9

3.6

4.4

4.4

6.5

8.5

DC voltage

Operations

→ Switching of DC current Page 5/96

Rated operational current I

e

open

DC-1 operation

60

V

I

e

A

20

20

20

20

35

40

110

V

I

e

A

20

20

20

20

35

40

220

V

I

e

A

15

15

15

15

35

40

440

V

I

e

A

1

1.3

1.3

1.3

2.9

2.9

DC-3 operation

60

V

I

e

A

20

20

20

20

35

35

110

V

I

e

A

20

20

20

20

35

35

220

V

I

e

A

1.5

1.5

1.5

1.5

10

10

440

V

I

e

A

0.2

0.2

0.2

0.2

0.6

0.6

DC-5 operation

60

V

I

e

A

20

20

20

20

35

35

110

V

I

e

A

20

20

20

20

35

35

220

V

I

e

A

1.5

1.5

1.5

1.5

10

10

440

V

I

e

A

0.2

0.2

0.2

0.2

0.6

0.6

DILM7 ... DILM170