Background Image
Table of Contents Table of Contents
Previous Page  78 / 133 Next Page
Information
Show Menu
Previous Page 78 / 133 Next Page
Page Background

TECHN I CAL DATA

S TANDARDS

216

100

SW3

125

SW3*

125/3

MS

200/3

MS

LIST No

100/21

BA

125/21

BA*

125/21

B

125/21

BDP

200/22

B

200/22

BDP

250/22

B

Rated current

100

A

125

A

125

A

125

A

200

A

200

A

250

A

Utilisation category AC22a

AC22a

AC22b

AC22b

AC22b

AC22b

AC22b

AC23b @63A

Rated voltage

240

V/415V

240

V/415V

415

V

240

V

415

V

240

V

415

V

Rated frequency 50Hz

50

Hz

50

Hz

50

Hz

50

Hz

50

Hz

50

Hz

Rated

500

V ac

500

V ac

500

V ac

500

V ac

500

V ac

500

V ac

500

V ac

insulation voltage

Rated impulse

6

kV ac peak

6

kV ac peak

6

kV ac peak

6

kV ac peak

6

kV ac peak

6

kV ac peak

6

kV ac peak

withstand voltage

Rated duty

Uninterrupted

Uninterrupted Uninterrupted Uninterrupted Uninterrupted Uninterrupted Uninterrupted

Rated short time 1.5kA rms

1.5

kA rms

5.5

kA rms

5.5

kA rms

5.5

kA rms

5.5

kA rms

5.5

kA rms

withstand current for 1 sec

for 1 sec

for 100ms

for 100ms

for 100ms

for 100ms

for 100ms

Rated short circuit 2.5kA peak

2.5

kA peak

8.0

kA peak

8.5

kA peak

8.5

kA peak

8.5

kA peak

8.5

kA peak

making capacity

Rated conditional

16.5

kA rms

16.5

kA rms

16

kA rms

16

kA rms

16

kA rms

9

kA rms

16

kA rms

short circuit

(

BS1361 100A fuse) (BS88 125A fuse) (BS88 160A fuse) (BS88 125A fuse) (BS88 200A fuse) (BS88 200A fuse) (BS88 200A fuse)

6

kA rms

(

BS88 250A fuse)

*

Rated conditional short circuit levels only apply when used as Incomer to Crabtree MCB Distribution Board and includes series connected outgoing MCB.

POLESTAR & LOADSTAR

Consumer units

BSEN60439-3

Distribution boards

BSEN60439-3

Control module enclosure

BSEN62208

Degree of protection

IP40 (IP20 with door open)

Switch disconnector

BSEN60947-3, IEC 60947-3

MCB

BSEN60898, IEC 60898

RCBO (MCB/RCD)

BSEN61009, IEC 61009

RCCB

BSEN61008, IEC 61008

Maximum terminal cable capacities

POLESTAR LOADSTAR

125

A (Heavy Duty)

70

mm

2 -

MCB

25

mm

2

35

mm

2

Switch disconnector (DP)

50

mm

2

50

mm

2

Switch disconnector (TP) 125A (Modular)

50

mm

2

50

mm

2

Switch disconnector (TP)

200

A

120

mm

2

120

mm

2

250

A

-

185

mm

2

RCCB

50

mm

2

50

mm

2

Earth busbar

16

mm

2

25

mm

2

Neutral busbar

16

mm

2

25

mm

2

Direct busbar connection

120

mm

2

120

mm

2

C50

Consumer units

BS5486, Part 13: 1989

Distribution boards

BS5486, Part 12: 1989

Degree of protection

IP20

Switch disconnector (DP)

BSEN60947-3, IEC 60947-3

Triple pole main switch

BS5419: 1977

MCB

BSEN60898, IEC 60898

Maximum terminal cable capacities

MCB

16

mm

2

Switch disconnector (DP)

50

mm

2

Triple pole main switch

50

mm

2

Earth busbar

16

mm

2

Neutral busbar

16

mm

2

STANDARDS COMPLIANCE

l

SWITCH DISCONNECTORS

l

A switch disconnector is defined in BSEN60947-3 as:

A switch which, in the open position, satisfies the isolating requirements specified for a disconnector”

IEC 60947–3 also defines a switch and a disconnector. In general terms the definitions cover a device that is capable of making, carrying and breaking normal

circuit currents, and may also be capable of carrying, for a specified time, abnormal loads such as short circuit currents. In the open position, the device will

provide isolation and it will indicate reliably the position of the contacts.

All Crabtree switch disconnectors rated in the following table comply with BSEN60947-3 and IEC 60947-3.