TECHN I CAL DATA
S TANDARDS
216
100
SW3
125
SW3*
125/3
MS
200/3
MS
LIST No
100/21
BA
125/21
BA*
125/21
B
125/21
BDP
200/22
B
200/22
BDP
250/22
B
Rated current
100
A
125
A
125
A
125
A
200
A
200
A
250
A
Utilisation category AC22a
AC22a
AC22b
AC22b
AC22b
AC22b
AC22b
AC23b @63A
Rated voltage
240
V/415V
240
V/415V
415
V
240
V
415
V
240
V
415
V
Rated frequency 50Hz
50
Hz
50
Hz
50
Hz
50
Hz
50
Hz
50
Hz
Rated
500
V ac
500
V ac
500
V ac
500
V ac
500
V ac
500
V ac
500
V ac
insulation voltage
Rated impulse
6
kV ac peak
6
kV ac peak
6
kV ac peak
6
kV ac peak
6
kV ac peak
6
kV ac peak
6
kV ac peak
withstand voltage
Rated duty
Uninterrupted
Uninterrupted Uninterrupted Uninterrupted Uninterrupted Uninterrupted Uninterrupted
Rated short time 1.5kA rms
1.5
kA rms
5.5
kA rms
5.5
kA rms
5.5
kA rms
5.5
kA rms
5.5
kA rms
withstand current for 1 sec
for 1 sec
for 100ms
for 100ms
for 100ms
for 100ms
for 100ms
Rated short circuit 2.5kA peak
2.5
kA peak
8.0
kA peak
8.5
kA peak
8.5
kA peak
8.5
kA peak
8.5
kA peak
making capacity
Rated conditional
16.5
kA rms
16.5
kA rms
16
kA rms
16
kA rms
16
kA rms
9
kA rms
16
kA rms
short circuit
(
BS1361 100A fuse) (BS88 125A fuse) (BS88 160A fuse) (BS88 125A fuse) (BS88 200A fuse) (BS88 200A fuse) (BS88 200A fuse)
6
kA rms
(
BS88 250A fuse)
*
Rated conditional short circuit levels only apply when used as Incomer to Crabtree MCB Distribution Board and includes series connected outgoing MCB.
POLESTAR & LOADSTAR
Consumer units
BSEN60439-3
Distribution boards
BSEN60439-3
Control module enclosure
BSEN62208
Degree of protection
IP40 (IP20 with door open)
Switch disconnector
BSEN60947-3, IEC 60947-3
MCB
BSEN60898, IEC 60898
RCBO (MCB/RCD)
BSEN61009, IEC 61009
RCCB
BSEN61008, IEC 61008
Maximum terminal cable capacities
POLESTAR LOADSTAR
125
A (Heavy Duty)
70
mm
2 -
MCB
25
mm
2
35
mm
2
Switch disconnector (DP)
50
mm
2
50
mm
2
Switch disconnector (TP) 125A (Modular)
50
mm
2
50
mm
2
Switch disconnector (TP)
200
A
120
mm
2
120
mm
2
250
A
-
185
mm
2
RCCB
50
mm
2
50
mm
2
Earth busbar
16
mm
2
25
mm
2
Neutral busbar
16
mm
2
25
mm
2
Direct busbar connection
120
mm
2
120
mm
2
C50
Consumer units
BS5486, Part 13: 1989
Distribution boards
BS5486, Part 12: 1989
Degree of protection
IP20
Switch disconnector (DP)
BSEN60947-3, IEC 60947-3
Triple pole main switch
BS5419: 1977
MCB
BSEN60898, IEC 60898
Maximum terminal cable capacities
MCB
16
mm
2
Switch disconnector (DP)
50
mm
2
Triple pole main switch
50
mm
2
Earth busbar
16
mm
2
Neutral busbar
16
mm
2
STANDARDS COMPLIANCE
l
SWITCH DISCONNECTORS
l
A switch disconnector is defined in BSEN60947-3 as:
“
A switch which, in the open position, satisfies the isolating requirements specified for a disconnector”
IEC 60947–3 also defines a switch and a disconnector. In general terms the definitions cover a device that is capable of making, carrying and breaking normal
circuit currents, and may also be capable of carrying, for a specified time, abnormal loads such as short circuit currents. In the open position, the device will
provide isolation and it will indicate reliably the position of the contacts.
All Crabtree switch disconnectors rated in the following table comply with BSEN60947-3 and IEC 60947-3.