Background Image
Table of Contents Table of Contents
Previous Page  76 / 133 Next Page
Information
Show Menu
Previous Page 76 / 133 Next Page
Page Background

TECHN I CAL DATA

RCD s

214

SPECIFICATION

l

BSEN61008

(

Voltage independent)

Range of current ratings 16–100A

Range of sensitivities

10–300

mA

Operation General

Type A or AC

Selective Type S (Time Delay)

Pole configurations

DP and TP&N

Voltage ratings DP

230

V

TP&N 240V/415V

Frequency ratings

50/60

Hz

OPERATION

l

The RCD employs the current balance principle which involves the supply

conductors to the load (phase and neutral) being wound onto a common

transformer core to form the primary windings. The secondary winding of the

current transformer is then connected to the electro-magnetic relay. Under

healthy circuit conditions, the current in the phase conductor is equal to the

current in the neutral and the vector sum of the current is zero. In the event

of an earth fault, an amount of current will flow to earth, creating an out of

balance situation in the transformer assembly. This out of balance is detected

by the secondary winding of the transformer and at a pre-determined level of

out of balance will activate the trip mechanism.

Single phase and neutral or three phase and neutral units (suitable for 3 or 4

wire systems) are available, the latter being suitable for balanced or

unbalanced 3 phase loads.

The RCD trip mechanism will operate at a residual current of between

50–100%

of its rated tripping current (sensitivity).

TEST BUTTON

l

A test button is provided on all RCDs to enable the operation of the device to

be checked.

It is recommended that an RCD is tested at least quarterly. (See BS7671)

Regulation 514-12-02.

RCDs

l

APPLICATIONS

l

Residual Current Devices (RCDs) may be required for one of two main

reasons:

(

a) to ensure the compliance of an installation with BS7671.

An RCD may be installed to meet the requirements where a high earth fault

loop impedance disqualifies the use of overcurrent protection devices as a

means of providing protection against indirect contact. To comply with

Regulation 413-02-16 the earth fault loop impedance in ohms multiplied

by the rated tripping current of the RCD in amperes must not exceed 50.

With the RCD having a sensitivity of 30mA, the maximum permissible

earth fault loop impedance is calculated as follows:

Z

S

(

max)=50/0.03=1666 Ohms

Rated tripping current

Max permissible

of RCD

earth fault loop impedance

30

mA

1666

Ohms

100

mA

500

Ohms

300

mA

166

Ohms

(

b) to provide a higher degree of protection than that given by direct

earthing, against fire or shock risks caused by earth leakage currents.

Overcurrent protection devices cannot detect earth fault currents below their

operating current. If they are the only means of earth fault protection, it is

possible for sufficient earth fault current to flow undetected to constitute a

fire risk.

By using an RCD, the flow of the sustained earth fault current, above the

tripping current of the RCD, is prevented. The shock risk associated with these

earth fault currents is also greatly reduced.

For personnel protection, a high sensitivity RCD with a maximum tripping

current of 30mA should be used. This is particularly important with portable

appliances where there is a danger of losing earth continuity due to damage

or fatigue.

Residual current devices are completely selective in their operation. They are

unaffected by parallel earth paths and are thus ideally suitable for the

protection of installations in modern high density dwellings or office blocks.

They are virtually tamperproof and provide a predetermined level of

protection. Even if earthing conditions deteriorate substantially, they will

continue to provide a higher degree of protection than would have been

given by direct earthing.

SENSITIVITIES

l

The choice of RCD depends upon the application of the degree of protection

required.

300

mA

provide the means to achieve compliance with the Wiring Regulations

in conditions of poor earth loop impedance and also give a good level of fire

risk protection.

100

mA

provide the means to achieve compliance with the Wiring

Regulations, a high level of fire risk protection and a degree of indirect shock

risk protection.

30

mA

for use where a higher degree of protection is required, with portable

equipment or equipment used in hazardous conditions. BS7671 regulation

471-16-01

indicates that where a socket outlet may reasonably be expected

to supply equipment to be used outside the zone, protection shall be afforded

by a residual current device having a rated residual operating current not

exceeding 30mA.

If using RCDs in series, discrimination can only be achieved by using Type S

devices in series with Types A or AC. See chart below.

TRANSIENT EARTH LEAKAGE CURRENTS

l

All Crabtree residual current devices incorporate a high degree of immunity

to tripping when subjected to transient earth leakage currents.

Such transients can occur when there is a significant level of capacitance to

earth as can result from cable capacitance (particularly MICC) or RF filter

networks. Crabtree RCDs are therefore less susceptible to nuisance tripping

due to transient earth leakage currents.

Test button

Test resistor

Incoming

supply

Load

circuits

Trip

relay

L1

N

L1

N

L2

L3

L2

L3

Test button

Test resistor

Incoming

supply

Load

circuits

Trip

relay

L

N

L

N

RCD circuit diagram (double pole)

Note

Exposed installation

metal work must be

earthed.

Note

Exposed installation

metal work must be

earthed.

RCD circuit diagram (triple pole and neutral)

BSEN61008-1:1995

l

Rated Residual Current (In)

Tripping

Type of RCD RCD to Trip between

times

50%-100%

I

n

1

x

I

n

2

x

I

n

5

x

I

n

500

Amps

Scope

Standard

Any Value, eg 10, 30, 100mA 300ms 150ms 40ms

40

ms

Maximum-Trip

A & AC

Time Delay

Greater than 30mA, eg 100mA

500

ms 200ms 150ms

150

ms Maximum-Trip

(

S)

130

ms 60ms 50ms

40

ms Minimum-Non Trip