Background Image
Table of Contents Table of Contents
Previous Page  74 / 133 Next Page
Information
Show Menu
Previous Page 74 / 133 Next Page
Page Background

TYPE CLASSIFICATION

l

BSEN60898 specifies different tripping characteristics for different types of

MCB, depending on the level of overload current required to make the MCB

trip out in less than 100 milliseconds. Crabtree Polestar and Loadstar MCBs

are available as types B, C or D, enabling installation designers to choose an

MCB with a characteristic closely matched to the circuit requirement.

C50 range is available as type C only.

FAULT LEVELS

l

Regulation 432–02–01 of BS7671 requires that a device providing protection

against overload currents and fault currents shall be capable of breaking any

overcurrent up to and including the prospective fault current at the point

where the device is installed.

In domestic situations this could be as high as 16kA, in industrial situations it

could be even higher.

According to regulation 434–03–01, the prospective fault current can be

higher than the breaking capacity of the protective device if another

protective device having the necessary breaking capacity is installed on the

supply side.

This means that MCBs can be backed up by devices of greater capacity such

as HRC fuses.

Crabtree Polestar Type B & C, Polestar Type D and Loadstar ‘H’ Types B, C & D,

Loadstar ‘F’ Types B, C & D and C50 MCBs can protect installations with

prospective currents up to 16kA, 10kA, 6kA and 4.5kA respectively without

the need for back-up devices.

When providing back-up protection, consideration must be given to

discrimination. Discrimination is said to occur when the device nearest the

fault operates first.

AMBIENT TEMPERATURE CONSIDERATIONS

l

Polestar and Loadstar MCBs are calibrated to meet the requirements of

BS EN 60898, 30°C Ref Calibration Temperature. At other temperatures the

following rating factors should be used:

At 60°C 0.9

At 20°C 1.0

At 0°C 1.1

Adjacent thermal-magnetic MCBs should not be continuously loaded at or

near their nominal rated currents when mounted in enclosures. It is good

engineering practice to either apply generous de-rating factors or make

provision for adequate free air between devices. In common with other

manufacturers, we recommend a 66% diversity factor is applied to the MCB

nominal rated current where it is intended to load adjacent MCBs

continuously (in excess of 1 hour).

The C50 Range of MCBs meet the requirements of BS EN 60898 for 30°C Ref

calibration temperature, but are virtually unaffected by ambient temperature

variations over their working range from below freezing to 55°C

MCBs – GENERAL

l

Crabtree Polestar, Loadstar and C50 range of MCBs comply fully with BSEN60898 and therefore enable the

requirements of BS7671, formerly the IEE Wiring Regulations to be met.

INDIRECT SHOCK RISK PROTECTION

l

BS7671, requires that measures are taken to protect against the risk of

electric shock, which can be the result of contact with live parts.

MCBs can be used in conjunction with earthed equipotential bonding to

achieve the required disconnection times of 0.4 seconds for 230V socket

outlets and 5 seconds for circuits supplying fixed equipment (Regulation

413–02–08).

This regulation, together with tables 41B1, 41B2 and 41D,

specifies the maximum permissible earth fault loop impedance which is

allowed using various protective devices. For unspecified ratings the formula

of Regulation 413-02-08 should be used.

EARTH FAULT LOOP IMPEDANCES (Z

S

)

TO GIVE COMPLIANCE WITH

BS7671 REGULATION 413-02-08 AT 230V

Maximum earth fault loop impedance in ohms for circuits supplying socket

outlets (also fixed equipment in bathrooms)

RATINGS

DEVICE

5

A 10A 15A 20A 30A 40A 45A 50A 60A

Rewireable Fuse BS3036 10.0

2.67 1.85 1.14

0.62

Cartridge Fuse BS1361 10.9

3.43 1.78 1.20

0.60

Type C MCB BSEN60898 4.80 2.40 1.60 1.20 0.80 0.60 0.53 0.48 0.40

RENARD SERIES OF RATINGS

DEVICE

6

A 10A 16A 20A 32A 40A 50A 63A

HRC fuse BS88

8.89 5.33 2.82 1.85 1.09 0.86 0.63 –

Type B MCB BSEN60898 8 4.8 3 2.4 1.5 1.2 0.96 0.76

Type C MCB BSEN60898 4 2.4 1.5 1.2 0.75 0.60 0.48 0.38

Type D MCB BSEN60898 2.0 1.2 0.75 0.6 0.38 0.3 0.24 0.19

At these values of loop impedance fuses will operate within 0.4 seconds and

MCBs will operate in 0.1 second.

The loop impedances given in the tables should not be exceeded when the

conductors are at their normal operating temperatures. If the conductors are

at a different temperature when tested, the reading should be adjusted

accordingly.

TECHN I CAL DATA

MCB s

212

RMS PROSPECTIVE CURRENT AS A MULTIPLE OF RATED CURRENT

OPERATING TIME IN SECONDS

2

HRS

1

HR

1,000

100

10

1.0

0.1

0.01

0.001

1

3 5 10 20

100

1,000

Type

B

Type

C

Type

D

POLESTAR & LOADSTAR MCBs