Background Image
Table of Contents Table of Contents
Previous Page  77 / 133 Next Page
Information
Show Menu
Previous Page 77 / 133 Next Page
Page Background

TECHN I CAL DATA

RCBO s

215

SPECIFICATION

l

RCBOs (MCB/RCD)

POLESTAR

LOADSTAR

Standards

BS4293/BS3871

BSEN61009

Short circuit breaking capacity 10kA

10

kA or 6kA

Current rating

6

to 40A

6

to 40A

MCB Type classification

C

C

RCD Type classification

AC

A

Rated voltage & frequency

240

V 50Hz

240

V 50Hz

RCD Tripping principle

Electromechanical

Electronic

Neutral configuration

Switched

Solid

Positive contact indication Yes

Yes

Loss of supply Neutral

Inherent

Via functional earth

circuit

APPLICATIONS

l

RCBOs provide both earth fault and overcurrent protection. For commercial

and industrial applications a unit should be employed, utilising Type C

(5–10

I

n) classification of MCB. RCBOs, other MCB classifications available

to order.

Polestar and 2 module Loadstar RCBOs employ an electromechanical

operating principle.

Loadstar 1 module RCBOs employ an electronic operating principle

incorporating loss of supply neutral protection via a functional earth lead.

All RCBOs give a high level of protection to individual circuits whilst exhibiting

improved immunity to response caused by transients.

Two module switched neutral RCBOs have safety advantages over single

module RCBOs and are exclusively used in continental Europe.

ADVANTAGES OF SWITCHED NEUTRAL RCBOs

l

If a neutral to earth fault occurs in a circuit fed via an RCBO with a solid

neutral which is backed up by an upstream selective RCD, the selectivity or

discrimination will be lost and the main RCD will also trip as it will still detect

the fault which has not been cleared.

The main requirements of RCD protection are:

Additional protection against direct contact with live parts

Protection against direct connection with live parts

Protection against fire in the case of a fault to earth

If a fault occurs between neutral and earth where a solid neutral RCBO is

protecting a circuit, the RCBO will trip. However, as previously stated, the

fault will still be in the circuit within the rest of the installation.

As the neutral will be common throughout the installation, it is possible that

current could still flow through the fault and lead to a fire hazard. This would

mean that the RCBO would not offer full protection against fire and therefore

does not comply with one of it’s main protection requirements.

Testing of outgoing circuits is easier with RCBOs incorporating a switched

neutral as an electrician does not have to disconnect terminals before testing.

BS7671 requires that the main switch to a TT earthed installation must have a

switched neutral.

INSTALLATION TESTING –

CAUTION

l

As Single Module RCBOs employ electronic components they should

be disconnected when carrying out the following tests on the electrical

installation:

(

a) Earth fault loop impedance test

The load terminals should be disconnected if it is intended to parallel-out the

unit for test purposes.

It may incur damage if mains potential is maintained on the load terminals of

this unit after the trip mechanism has operated.

(

b) Insulation test

Whilst RCBOs can withstand the effects of normal insulation testers without

damage, false readings may be given on the test instrument. For this reason

it is recommended that the device is disconnected during this test.

RCBOs (MCB/RCDs) & RCDs – GENERAL

l

IEC PUBLICATION 60479 CURVES WITH CRABTREE RCD CHARACTERISTICS SUPERIMPOSED

l

TIME/CURRENT ZONES OF EFFECTS OF AC CURRENT (15–100Hz) ON PERSONS

Zone Physiological effects

1

Usually no reaction

4

In addition to the effects

effects.

of zone 3, probability of

ventricular fibrillation

2

Usually no harmful

increased up to 5%

physiological effects.

(

Curve C2) up to 50%

(

Curve C3) and above

3

Usually no organic

50%

beyond Curve C3.

damage to be expected.

Increasing with magnitude

Likelihood of muscular

and time, pathyphysio-

contraction and difficulty

logical effects such as

of breathing, reversible

cardiac arrest, breathing

disturbances of formation

arrest and heavy burns

and conduction of

may occur.

impulses in the heart, and

transient cardiac arrest

without ventricular

fibrillation increases with

current magnitude and

time.

10,000

5,000

2000

1000

500

200

100

50

20

10

0.1 0.2 0.3 0.5 1 2 3 5 10 20 30 50 100 200 300 500 1,000 2,000

10,000

5,000

3,000

Current in milliamperes (RMS)

100

mA

30

mA

Typical current

Limits due to body resistance

at 230V

1

2

3

4

a

b

c

1

c

2

c

3

IEC 60479

Time in milliseconds