TECHN I CAL DATA

POL E S TAR MCB AP P L I CAT I ON

219

TYPE B TYPICAL TRIPPING TIMES

l

RATING CURRENT REQUIRED TO OPERATE

(

A)

60

s 10s 5s 4s 3s 2s 1s 0.4s 0.1s 0.02s

6

12 23 24 24 24 24 24 24 24 24

10

19 32 40 40 40 40 40 40 40 40

16

30 50 64 64 64 64 64 64 64 64

20

40 68 80 80 80 80 80 80 80 80

32

67 112 128 128 128 128 128 128 128 128

40

80 120 160 160 160 160 160 160 160 160

50

100 160 200 200 200 200 200 200 200 200

63

138 230 252 252 252 252 252 252 252 252

TYPE C TYPICAL TRIPPING TIMES

l

RATING CURRENT REQUIRED TO OPERATE

(

A)

60

s 10s 5s 4s 3s 2s 1s 0.4s 0.1s 0.02s

6

12 23 33 37 44 45 45 45 45 45

10

19 32 48 55 67 75 75 75 75 75

16

30 50 67 72 83 100 120 120 120 120

20

40 68 92 104 120 150 150 150 150 150

32

67 112 144 153 176 208 240 240 240 240

40

80 120 152 168 190 230 300 300 300 300

50

100 160 210 230 260 312 375 375 375 375

63

138 220 283 302 334 397 472 472 472 472

TYPE D TYPICAL TRIPPING TIMES

l

RATING CURRENT REQUIRED TO OPERATE

(

A)

60

s 10s 5s 4s 3s 2s 1s 0.4s 0.1s 0.02s

6

12 23 33 37 44 55 90 90 90 90

10

19 32 48 55 67 93 150 150 150 150

16

30 50 67 72 83 100 147 240 240 240

20

40 68 92 104 120 150 240 300 300 300

32

67 112 144 153 176 208 288 432 480 480

40

80 120 152 168 190 230 340 600 600 600

50

100 160 210 230 260 312 450 750 750 750

63

138 220 283 302 334 397 555 819 945 945

POLESTAR MCBs – Type B, C & D typical tripping times/I

2

t energy let-through values

l

TOTAL I

2

t LEVELS

l

CABLE CONDUCTOR SIZES

50&63

A

40

A

32

A

20

A

16

A

10

A

6

A

2.5

mm

2

1.5

mm

2

1.0

mm

2

10

5

10

4

10

3

0.1

1.0

10.016.0

100.0

2

t energy let-through in A

2

s

(50

Hz sine wave)

one complete

1

/

2

cycle.

PROSPECTIVE FAULT CURRENT (kA)

TOTAL LET-THROUGH ENERGY (

2

t)

NOTE

Tests performed at 240V 50Hz at most unfavourable closing angle, ie +60°.

TYPICAL VALUES OF I

2

t ENERGY LET-THROUGH

FOR POLESTAR MCBs

l

TOTAL I

2

t LET-THROUGH (A

2

SEC)

MCB RATING

6

kA

10

kA

16

kA

6

8000

12000

16000

10

15000

25000

34000

16

20000

35000

53000

20

25000

40000

64000

32

28000

50000

70000

40

30000

65000

85000

50

36000

75000

110000

63

36000

75000

110000