Background Image
Table of Contents Table of Contents
Previous Page  84 / 133 Next Page
Information
Show Menu
Previous Page 84 / 133 Next Page
Page Background

TECHN I CAL DATA

LOADS TAR

222

SHORT CIRCUIT CURRENT AS A MULTIPLE OF RATED CURRENT

OPERATING TIME IN SECONDS

2

HRS

1

HR

1,000

100

10

1.0

0.1

0.01

0.001

1

3 5 10 20

100

1,000

Type

B

Type

C

Type

D

DISTRIBUTION BOARDS

l

Standards Compliance:

BSEN60439-3 and IEC 60439-3

Rated Voltage:

230/400

V, 50/60Hz

Rated Current:

125/250

A

Rated Insulation Voltage:

500

V a.c.

Short Circuit Withstand:

16

kA Conditional

Protection Degree:

BSEN60529 IP4X (Door Closed)

IP3X (Door Open)

MINIATURE CIRCUIT BREAKERS (MCBs)

l

Standards Compliance:

EN60898 and IEC 60898

Rated Voltage:

230/400

V, 50/60Hz

Short Circuit Capacity:

6

kA or 10kA (EN60898 and IEC60898).

Tripping Class:

Types B, C and D

Temperature Range:

Maximum Operating Temperature: 55˚C

Pole Configuration:

Single Pole, Double Pole, Triple Pole

ISOLATORS & SWITCH DISCONNECTORS

l

Standards Compliance:

BSEN60947-3 and IEC 60947-3

Rated Voltage:

230/400

V, 50/60HZ

Rated Insulation Voltage:

500

V a.c.

Rated Impulse Withstand Voltage:

4

kV a.c. peak

Rated Duty:

63

to 125A Modular

AC 22A (63A at AC23B)

Heavy Duty 200/250A

AC 22B

RESIDUAL CURRENT CIRCUIT BREAKERS (RCCBs)

l

Standards Compliance:

EN61008 and IEC 61008

Rated Voltage:

230/400

V, 50/60Hz

Tripping Characteristic:

AC

MOULDED CASE CIRCUIT BREAKERS (MCCBs)

l

Standards Compliance:

BSEN60947-2 and IEC 60947-2

Rated Voltage:

415

V, 50/60Hz

Rated Insulation Voltage:

500

V a.c.

Rated Ultimate Short Circuit Capacity (Icu):

25

kA (G Frame)

25

kA (J Frame)

Rated Service Short Circuit Capacity (Ics):

50%

of Icu (G Frame)

75%

of Icu (J Frame)

MAXIMUM TERMINAL CAPACITIES

l

MCB

35

mm

2

RCCB

50

mm

2

Isolators 63 to 125A

50

mm

2

200

A Heavy Duty

120

mm

2

250

A Heavy Duty

185

mm

2

via sockets

MCCB 200A Frame

120

mm

2

(

Stranded)

RCBOs

l

Single module

Standards Compliance:

EN61009, IEC 601009

Rated Voltage:

230

V 50Hz

Rated Short Circuit Capacity:

6

kA or 10kA

MCB Tripping:

Type C

RCD Tripping (Electronic):

Type A

Neutral:

Unswitched

Neutral flying lead and functional earth lead provided

Two module

Standards Compliance:

EN61009, IEC601009

Rated Voltage:

230

V 50Hz

Rated Short Circuit Capacity:

6

kA or 10kA

MCB Tripping:

Type C

RCD Tripping: (Electromechanical)

Type AC

Neutral

Switched

Neutral flying lead provided

TYPE CLASSIFICATION

l

BSEN60898 specifies different tripping characteristics for different types of

MCB, depending on the level of overcurrent required to make the MCB trip

out in less than 100 milliseconds. Crabtree MCB’s are available as types B, C

or D, enabling installation designers to choose an MCB with a characteristic

closely matched to the circuit requirement.

LOADSTAR RANGE

l

Crabtree Loadstar MCBs comply fully with BSEN60898 and and therefore enable the requirements of

BS7671 to be met.

A C

B

MCB

RCCB

D

E

E

MINIATURE CIRCUIT BREAKERS (MCBs)

l

A

B

*

C

D

E

Single pole

43.8 56.5 13.5

86

18

Double pole

43.8 56.5 13.5

86

36

Triple pole

43.8 56.5 13.5

86

54

RESIDUAL CURRENT CIRCUIT BREAKERS (RCCB)

l

A

B

C

D

E

2

pole

43.8 56.5 13.5

86

36

4

pole

43.8 56.5 13.5

86

72