TECHN I CAL DATA
LOADS TAR
222
SHORT CIRCUIT CURRENT AS A MULTIPLE OF RATED CURRENT
OPERATING TIME IN SECONDS
2
HRS
1
HR
1,000
100
10
1.0
0.1
0.01
0.001
1
3 5 10 20
100
1,000
Type
B
Type
C
Type
D
DISTRIBUTION BOARDS
l
Standards Compliance:
BSEN60439-3 and IEC 60439-3
Rated Voltage:
230/400
V, 50/60Hz
Rated Current:
125/250
A
Rated Insulation Voltage:
500
V a.c.
Short Circuit Withstand:
16
kA Conditional
Protection Degree:
BSEN60529 IP4X (Door Closed)
IP3X (Door Open)
MINIATURE CIRCUIT BREAKERS (MCBs)
l
Standards Compliance:
EN60898 and IEC 60898
Rated Voltage:
230/400
V, 50/60Hz
Short Circuit Capacity:
6
kA or 10kA (EN60898 and IEC60898).
Tripping Class:
Types B, C and D
Temperature Range:
Maximum Operating Temperature: 55˚C
Pole Configuration:
Single Pole, Double Pole, Triple Pole
ISOLATORS & SWITCH DISCONNECTORS
l
Standards Compliance:
BSEN60947-3 and IEC 60947-3
Rated Voltage:
230/400
V, 50/60HZ
Rated Insulation Voltage:
500
V a.c.
Rated Impulse Withstand Voltage:
4
kV a.c. peak
Rated Duty:
63
to 125A Modular
AC 22A (63A at AC23B)
Heavy Duty 200/250A
AC 22B
RESIDUAL CURRENT CIRCUIT BREAKERS (RCCBs)
l
Standards Compliance:
EN61008 and IEC 61008
Rated Voltage:
230/400
V, 50/60Hz
Tripping Characteristic:
AC
MOULDED CASE CIRCUIT BREAKERS (MCCBs)
l
Standards Compliance:
BSEN60947-2 and IEC 60947-2
Rated Voltage:
415
V, 50/60Hz
Rated Insulation Voltage:
500
V a.c.
Rated Ultimate Short Circuit Capacity (Icu):
25
kA (G Frame)
25
kA (J Frame)
Rated Service Short Circuit Capacity (Ics):
50%
of Icu (G Frame)
75%
of Icu (J Frame)
MAXIMUM TERMINAL CAPACITIES
l
MCB
35
mm
2
RCCB
50
mm
2
Isolators 63 to 125A
50
mm
2
200
A Heavy Duty
120
mm
2
250
A Heavy Duty
185
mm
2
via sockets
MCCB 200A Frame
120
mm
2
(
Stranded)
RCBOs
l
Single module
Standards Compliance:
EN61009, IEC 601009
Rated Voltage:
230
V 50Hz
Rated Short Circuit Capacity:
6
kA or 10kA
MCB Tripping:
Type C
RCD Tripping (Electronic):
Type A
Neutral:
Unswitched
Neutral flying lead and functional earth lead provided
Two module
Standards Compliance:
EN61009, IEC601009
Rated Voltage:
230
V 50Hz
Rated Short Circuit Capacity:
6
kA or 10kA
MCB Tripping:
Type C
RCD Tripping: (Electromechanical)
Type AC
Neutral
Switched
Neutral flying lead provided
TYPE CLASSIFICATION
l
BSEN60898 specifies different tripping characteristics for different types of
MCB, depending on the level of overcurrent required to make the MCB trip
out in less than 100 milliseconds. Crabtree MCB’s are available as types B, C
or D, enabling installation designers to choose an MCB with a characteristic
closely matched to the circuit requirement.
LOADSTAR RANGE
l
Crabtree Loadstar MCBs comply fully with BSEN60898 and and therefore enable the requirements of
BS7671 to be met.
A C
B
MCB
RCCB
D
E
E
MINIATURE CIRCUIT BREAKERS (MCBs)
l
A
B
*
C
D
E
Single pole
43.8 56.5 13.5
86
18
Double pole
43.8 56.5 13.5
86
36
Triple pole
43.8 56.5 13.5
86
54
RESIDUAL CURRENT CIRCUIT BREAKERS (RCCB)
l
A
B
C
D
E
2
pole
43.8 56.5 13.5
86
36
4
pole
43.8 56.5 13.5
86
72