PROSPECTIVE CURRENT

100,000

TECHN I CAL DATA

G MCCB

228

PhaseCtrs PhaseCtrs

78.50

33.50

70.50

77.50

83.50

97.00

max

Terminals Suitable for

10

mm Strip or 70mm

2

Cable

Operating Lever Positions

'

I' Breaker Closed

'

O' Breaker Open

'

T' Breaker Tripped by Release

'

R' Reset Positions from Tripped

I

T

O

R

26.25

26.25

Use M4

Fasteners

94.00

Fixing Ctrs

Fixing Ctrs

120.00

30.00

26.25

Interphase Barriers

Use M3

Fasteners

19.50

74.00

Fixing Ctrs

Fixing Ctrs

120.00

26.00

POWERSTAR G FRAME MAXIMUM EARTH LOOP IMPEDANCES Zs (ohms) for Uo = 240V~

Current Rating (A)

16

20

25

32

40

50

63

80

100 125

0.4

Seconds Disconnection Time 0.48

Ω

0.48

Ω

0.48

Ω

0.48

Ω

0.48

Ω

0.48

Ω

0.30

Ω

0.30

Ω

0.24

Ω

0.24

Ω

5.00

Seconds Disconnection Time 1.68

Ω

1.37

Ω

1.06

Ω

0.81

Ω

0.69

Ω

0.51

Ω

0.37

Ω

0.32

Ω

0.27

Ω

0.25

Ω

G FRAME MCCBs TECHNICAL SPECIFICATION

l

G FRAME SPECIFICATION

I

Specification

BSEN60947-2

Current Range

16 – 125

A

Ue Rated Operation Voltage

240

V SP 415V TP

Ui Rated Insulation Voltage

500

V AC

Rated Frequency

50/60

Hz

Release

Thermal Magnetic

Adjustment

None

Ambient Range

-20

°C to 55°C

Humidity Range

0 – 90%

Weight

SP - 0.4kg TP - 0.95kg

Mechanical Duration

8000

operations

FEATURES

I

The symmetrical vertical and horizontal axis with

a double stepped escutcheon plate, enabling it to

fit through either a 46mm or 80mm cut-out.

A double insulated compartment located behind

the removable escutcheon plate, facilities easy

on-site installation of shunt trip and auxiliary

switch units.

AVAILABLE OPTIONS

I

ST (See Product Section for selection)

Aux Switches

Padlocking

Terminal Shrouds

SHORT CIRCUIT BREAKING CAPACITY

I

Type

GB

GN

Ue

Icu

Icu

SP/TP

TP

220

V

30

30

380

V

16

25

415

V

16

25

Ics

= 50% Icu

INSTANTANEOUS TRIP BANDS

I

25 – 50

A

500

A

63 – 80

A

800

A

100 – 125

A

1000

A

TERMINALS

I

Front-connected clamps –

16

A to 125A – 70mm

2

cable

– 10

mm strip

AUXILIARY EQUIPMENT

I

G Frame MCCBs

a) Shunt Trip & Auxiliary Switch

b) Two Auxiliary Switches

(

For Shunt Trip with 2 Auxiliary C/O Switches add suffix A to ST List No.).

Shunt Trip

Max on time 1 cycle:

10

seconds

Max on time con. cycle: 6 seconds

24

V dc

30

W Closed Power

115

V ac

43

VA Consumption

230

V ac

43

VA 10% Duty Cycle

Auxiliary Contact Ratings (A)

Voltage Resistive Tungsten Load Inductive

Load (A) NC (A)

NO (A) Load (A)

AC

125

3

0.5

0.5

3

250

3

0.5

0.5

3

DC

30

3

3

0.5

3

50

1

0.7

0.7

1

125

0.5

0.4

0.4

0.05

}