TECHN I CAL DATA

J MCCB

230

JN & JM FRAME MCCBs TECHNICAL SPECIFICATION

l

JN & JM FRAME SPECIFICATION

I

Specification

BSEN60947-2

Current Range

25 – 200

A

Ue Rated Operation Voltage

240

V SP 415V TP

Ui Rated Insulation Voltage

660

V AC

Rated Frequency

50/60

Hz

Release

Thermal Magnetic

Thermal Adjustment

0.7 – 1.0

x Rated Current

Instantaneous Adjustment

Non-adjustable

Short Circuit Breaking Capacity

Icu at 415V = 25KA, Ics = 75%Icu

Ambient Range

-20

°C to 55°C

Humidity Range

0 – 90%

Weight

SP – 0.7Kg TP – 1.8Kg TP & Sw N – 2.4Kg

10

4

10

5

I

2

t

10

6

10

7

10

8

1000

10000

PROSPECTIVE CURRENT

100000

31

100

135

Position of

Terminal Shroud

46 77

35 35

35

105

140

91

83

29

178

154

23.5

135

25

92

POWERSTAR JN FRAME MAXIMUM EARTH LOOP IMPEDANCES Zs (ohms) for U

o

= 240V~

Current Rating (A)

16/20/25 32

40

50

63

80

100

125

160

200

0.4

Sec Disconnection Time 0.500

Ω

0.500

Ω

0.500

Ω

0.500

Ω

0.500

Ω

0.250

Ω

0.250

Ω

0.250

Ω

0.125

Ω

0.125

Ω

5.00

Sec Disconnection Time 0.500

Ω

0.500

Ω

0.500

Ω

0.500

Ω

0.500

Ω

0.250

Ω

0.250

Ω

0.250

Ω

0.125

Ω

0.125

Ω

POWERSTAR JM FRAME MAXIMUM EARTH LOOP IMPEDANCES Zs (ohms) for U

o

= 240V~

Current Rating (A)

50

63

80

100

125

160

200

0.4

Sec Disconnection Time 0.125

Ω

0.125

Ω

0.125

Ω

0.125

Ω

0.125

Ω

0.125

Ω

0.125

Ω

5.00

Sec Disconnection Time 0.125

Ω

0.125

Ω

0.125

Ω

0.125

Ω

0.125

Ω

0.125

Ω

0.125

Ω

FEATURES

I

From J Frame to N Frame Powerstar MCCBs

feature escutcheons of the same height allowing

any of the frame sizes to be grouped together in a

single panel cutout.

Front adjustable thermal tripping elements.

OPTIONS

I

ST UVR

Aux SW

Rotary Handle

Padlocking

Terminal Shrouds

• 4

th Poles when fitted are left hand side

(

See Product Section for selection)

SHORT CIRCUIT BREAKING CAPACITY

I

Ue

Icu

220

V

50

kA

380

V

32

kA

415

V

25

kA

Ics

= 75% Icu

INSTANTANEOUS TRIP BANDS

I

J Frame

JM Frame

25 – 63

A = 400A

80 – 125

A = 800A

160 – 200

A = 1600A 50 – 200 = 1600A

TERMINALS

I

Front-connected clamps –

25

A to 200A–120mm

2

solid/150mm

2

stranded

AUXILIARY EQUIPMENT OPTIONS

I

a) UVR & Auxiliary Switch

b) Shunt Trip & Auxiliary Switches

c) Two Auxiliary Switches each to change over

Shunt Trip Voltage Range

70 – 110%

Under Voltage Release Threshold 70 – 35%

UVR Power Pack

10

VA

(110

V & 415V units also supplied with transformer additional to Powerpack.).

Auxiliary Contact Ratings

Voltage Resist’

Tungsten Load Induct’

Load (A) NC (A)

NO (A) Load (A)

AC

125

10

2

1

10

250

10

1.5

1

10

DC

30

10

3

1.5

10

50

3

0.8

0.8 2.5

125

0.5

0.5

0.5 0.07