Background Image
Table of Contents Table of Contents
Previous Page  98 / 133 Next Page
Information
Show Menu
Previous Page 98 / 133 Next Page
Page Background

10

4

10

5

10

6

10

7

10

8

1000

10000

PROSPECTIVE CURRENT

100000

I

2

t

TECHN I CAL DATA

N MCCB

236

206

4

x 8mm

Fixing Holes

Alternative 'T' type

and front connected

terminals shown

Rear terminals can

be positioned

either vertically or

horizontally

but vertical,

as illustrated,

is recommended to

assist heat dissipation

140.5

85

94.5

354

395

141

92

210

70

10

C

34.5

212.5

61

28.5

0 8.5

8

100

mm min.

to earthed

metal

70

70

14

35.5

A A

63 25

56

B

0 17

A A

63 25

56

B

0 21

Rating A B C

800

A 70mm 45mm 12mm

1000

A 70mm 45mm 15mm

1250

A 82mm 60mm 15mm

1600

A 87mm 65mm 18mm

POWERSTAR N FRAME MAXIMUM EARTH LOOP IMPEDANCES Zs (ohms) for U

o

= 240V~

Current Rating (A)

800

1000

1250

1600

Magnetic Trip Setting

0.4

Seconds Disconnection Time

0.0242

Ω

0.0218

Ω

0.0218

Ω

0.0218

Ω

High

5.00

Seconds Disconnection Time

0.0727

Ω

0.0545

Ω

0.0545

Ω

0.0545

Ω

Low

N Frame MCCB Energy Let Through

N FRAME MCCB s TECHNICAL SPECIFICATION

l

N FRAME SPECIFICATION

I

Specification

BSEN60947-2

Current Range

800 – 1600

Amps

Uie Rated Operation Voltage

415

V

Ui Rated Insulation Voltage

660

V AC

Rated Frequency

50/60

Hz

Icu (415V) Short Circuit Breaking Capacity

50

kA

Thermal Adjustment

See Detail Page over

Instantaneous Adjustment

See Detail Page over

Ambient Range

-20

°C to 55°C

Humidity Range

0 – 90%

Weight

Rear Terminals 17kg

Front Flat 19kg

N FRAME FEATURES

I

From J Frame to N Frame Powerstar MCCB’s

feature escutcheons of the same height to simplify

switchboard installations.

Front adjustable thermal and instantaneous

tripping elements.

AVAILABLE OPTIONS

I

ST UVR

Aux SW

Key Interlock Direct Mounting

Rotary Handle

Padlocking

Dolly Extension

(

See Product Section for selection)

SHORT CIRCUIT BREAKING CAPACITY

I

Ue

Icu

220

V

70

kA

380

V

50

kA

415

V

50

kA

Ics

= 75% Icu

TERMINALS

I

Back connected units supplied with 6 tee

terminals which can be positioned either vertically

or horizontally.

Front connected units supplied with 6 front flat

terminals.

AUXILIARY EQUIPMENT OPTIONS

I

a) UVR & Auxiliary Switch

b) ST & Auxiliary Switch

c) N Frame 3 Auxiliary C/O Switches

Shunt Trip Voltage Range

70 – 110%

UVR Power Pack

10

VA

(110

v & 415V units supplied with Transformer in addition to Powerpack.).

Auxiliary Contact Ratings

Voltage Resist’

Tungsten Load Induct’

Load (A) NC (A)

NO (A) Load (A)

AC

125

3

0.5

0.5

3

250

3

0.5

0.5

3

DC

30

3

3

0.5

3

50

1

0.7

0.7

1

125

0.5

0.4

0.4 0.05

800

A-1600A Rear

T Type Terminal

800

A-1000A Front

1250

A-1600A Front