TECHN I CAL DATA
CE I CON
241
CONTACTOR SPECIFICATION
l
FEATURES
UNITS C3
C7
C10
C14
C19 C22
C30
C43 C63
Main poles
3
3
3
3
3
3
3
3
3
Auxiliary poles - standard
1
1
1
1
1
0
0
2
2
Rated impulse withstand voltage (Uimp)
Kv
6
6
6
6
6
6
6
6
6
Rated impulse withstand voltage (Ui) - main poles
V
690
690
690
690
690
690
690
690
690
Rated impulse withstand voltage (Ui) - Aux. poles
V
690
690
690
690
690
–
–
690
690
Rated operational current (Ie) 400/415V 50Hz
AC1 Non-inductive (@45 degrees)
A
20
20
25
25
25
35
35
75
85
AC3 Squirrel cage motors - normal switching
A
5
8.5
8.5
11
14
22
28
40
55
AC4 Squirrel cage motors - plugging/inching
A
5
8.5
8.5
8.3
11
14
22
28
40
Other ratings
Conventional thermal rating (ith) open @45 degrees)
A
20
20
25
25
25
35
35
75
85
Star-delta starter
A
–
–
14.4
19
24
–
–
69
95
Transformer primary switching
A
5
5.7
8.3
10
11
–
–
32
36
Tungsten and infra red lamps
A
–
4.5
8.5
10
13
–
–
37
48
Non-compensated high-pressure mercury, sodium A
–
8.5
8.5
11
18
–
–
44
50
vapour and halide lamps
Compensated high-pressure mercury, sodium
A
–
4.5
4.5
7
14
–
–
22
24
vapour and halide lamps
Capacitor switching (single bank only) 400/415V kVAr
–
–
–
–
–
–
–
17
25
Mechanical durability - number of operations
x10
6
10
10
10
10
10
10
10
3
3
Maximum operations per hour (AC3)
3000
3000
3000
3000
3000
3000
3000
3000
3000
Maximum HRC back up fuse links (50kA)
-
Type 2 co-ordination
A
20
20
–
–
–
–
–
–
–
-
Type 1 co-ordination
A
25
25
25
25
35
50
50
80
125
Rating of auxiliary poles and relays (AC15)
- 230/2400
V (Built in aux pole)
A
6
6
6
6
6
–
–
6
6
- 400/415
V
A
4
4
4
4
4
–
–
4
4
- 500
V
A
2
2
2
2
2
–
–
2
2
Operating coil voltage range
Consumption, ac coil varients
-
pull in VA
37
32
66
66
66
66
66
130
130
-
hold in VA 5.5
5.5
8
8
8
8
8
10
10
Average operating times, ac coil varients - pick up ms
6-12
6-12
–
–
–
–
–
10-20 10-20
-
drop out ms
5-10
5-10
–
–
–
–
–
8-15
8-15
Cable termination -maximum conductor size
Main pole terminals - single or stranded
mm 2.5
2.5
4
4
4
10
10
35
35
-
flexible
mm 2.5
2.5
2.5
2.5
2.5
6
6
25
25
Auxiliary pole terminals - single or stranded
mm 2.5
2.5
2.5
2.5
2.5
–
–
2.5
2.5
-
flexible
mm 2.5
2.5
2.5
2.5
2.5
–
–
2.5
2.5
Ambient temperature limits - open
deg C -20/+60 -20/+60 -20/+60 -20/+60 -20/+60 -20/+60 -20/+60 -20/+60 -20/+60
-
enclosed
deg C -20/+45 -20/+45 -20/+45 -20/+45 -20/+45 -20/+45 -20/+45 -20/+45 -20/+45
Weight
kg
0.16
0.18
0.3
0.3
0.3
0.32
0.32
0.93
0.93
OVERLOAD RELAYS SPECIFICATION
l
UNITS
51500/-
55500/-
57500/-
49500/-
Range - Direct on
A
0.3-12.5
0.15-16
0.15-40
0.15-40
-
Star delta
A
–
4.1-27.6
4.1-69
23-109
Rated impulse withstand voltage (Uimp)
kV
6
6
6
6
Rated insulation voltage (Ui) - main poles
V
690
690
690
690
-
auxiliary poles
V
500
500
500
500
Auxiliary contact rating AC15 -230/240V
A
2
3
3
2
- 400/415
V
A
1
2
2
1
- 500
V
A
0.5
1
1
0.5
Cable termination - maximum conductor size
Main pole terminals
-
single or stranded
mm
4
16
16
25
-
flexible
mm
4
10
10
16
Auxiliary pole terminals
-
single or stranded
mm
2.5
2.5
2.5
2.5
-
flexible
mm
1.5
1.5
1.5
1.5
Control circuit fuse maximum (normal or slow)
A
6
10
10
6
Ambient temperature limits - open
deg C
-20/
+55
-20/
+60
-20/
+60
-20/
+55
-
closed
deg C
-20/
+55
-20/
+40
-20/
+40
-20/
+55
Weight
kg
0.16
0.16
0.16
0.3
Maximum HRC back up fuse links (50kA)
Type 1 or type 2 co-ordination