TECHN I CAL DATA
CE I CON
242
CEICON C3–C63 OVERLOAD RELAYS
l
CEICON overload relays should be backed up by HRC fuse links
selected from the following table.
When selecting a motor rated fuse link the recommended rating relates to
the largest rated current, eg for an application requiring a 50A fuse link, a
motor rated fuse link marked 32M50 should be used.
OVERLOAD RELAY
FUSE LINK
RATING (A)
Type
LIST No series
Rating (A)
Type gL
MPSCC
C3/7
51500/
DC
0.3–0.45
2
80
kA
51500/
EC
0.45-0.67
2
80
kA
51500/
FC
0.67-1.0
4
80
kA
51500/
GC
1.0-1.5
6
80
kA
51500/
HC
1.4-2.1
6
80
kA
51500/
IC
1.8-2.7
10
80
kA
51500/
JC
2.4-3.6
10
80
kA
51500/
KC
3.5-5.0
16
80
kA
51500/
JC
4.0-6.0
20
80
kA
51500/
MC
5.5-8.5
20
80
kA
51500/
NC
8.5-12.5
25
80
kA
C10/30
55
or 57 500/BC 0.15–0.25
1
80
kA
55
or 57 500/CC 0.24–0.4
1
80
kA
55
or 57 500/DC 0.38–0.63
1
80
kA
55
or 57 500/FC 0.6–1
2
80
kA
55
or 57 500/GC 0.96–1.6
4
80
kA
55
or 57 500/HC 1.5–2.5
6
80
kA
55
or 57 500/JC 2.4–4
10
80
kA
55
or 57 500/KC 3.8–6.3
16
80
kA
55
or 57 500/MC 6–10
20
80
kA
55
or 57 500/NC 9.6–16
25
80
kA
57500/
PC
15–25
50
80
kA
57500/
QC
24–40
80
80
kA
C43/63
49500/
AD
13–21
50
80
kA
49500/
BD
16–25
50
80
kA
49500/
CD
21–32
63
80
kA
49500/
DD
25–40
80
80
kA
49500/
ED
32–50
100
80
kA
49500/
FD
50–63
125
80
kA
HRC BACK-UP FUSE LINKS, OVERLOAD RELAY CHARACTERISTICS & CONTACT LIFE
l
CEICON OVERLOAD RELAY CHARACTERISTICS
l
The 3-phase overload tripping characteristics are taken from a cold condition
in an ambient temperature of 20°C and are therefore worst case curves.
The tripping times should not be longer than those shown (it will be noted
that they apply over a range: curves for individual units will operate within a
narrower band).
It should be noted that the best single phasing protection is obtained when
the overload relay is operating at or near its maximum rating.
CONTACT LIFE FOR CEICON C3/181 CONTACTORS
l
C3/7 (class 10A)
C10/30 (class 10A)
C43/C63 (class 10A)
Severe conditions for squirrel-cage motors
Utilisation category AC4
OPERATING CHARACTERISTICS
Inching, reverse-power braking, plugging
Switching on: 6xFLC of motor
Switching off: 6xFLC of motor
TYPICAL APPLICATIONS
Printing presses, wire-drawing machines, centrifuges, special drives on manufac-
turing and processing machinery
Normal switching conditions for squirrel-cage motors
Utilisation category AC3
OPERATING CHARACTERISTICS
Switching on: From standstill 6xFLC of motor
Switching off: While running 1xFLC of motor
TYPICAL APPLICATIONS
Compressors, lifts, mixers, sluices, pumps, escalators, stirrers, barrels, blowers, con-
veyors, centrifuges, air-conditioning, general drives on manufacturing and process-
ing machinery
1 1.2 1.5 2 3 4 5 6 7 8
5
10
20
40
1
2
4
6
10
20
40
60
120
X setting current (Ir)
min
sec
min
sec
1 1.2 1.5 2 3 4 5 6 7 8
5
10
20
40
1
2
4
6
10
20
40
60
120
X setting current (Ir)
1 1.2 1.5
3 4 5 6 7 8
5
10
20
40
1
2
4
6
10
20
40
60
X setting current (Ir)
2
min
sec
120
C22: 2x10
6
switching cycles (= 2 million)
3
2
1
0.7
0.5
0.4
0.3
0.55 1.1 2.2 4 7.5 15 30 55 90 160 315
0.75 1.5 3 5.5 11 22 45 75 132 200 400
kW
C3
7
10 19
14
30
22 43
63
415
V rating
Switching
cycles
x10
6
Ceicon contactor type
Max
600
ops/hr
Ceicon contactor type
Example: 7.5kW C19: 0.9x10
6
switching cycles (= 900 thousand)
C19: 1x10
6
switching cycles (= 1 million)
0.75 1.5 3 5.5 11 22 45 75110220
kW
415
V rating
1.1 2.2 4 7.5 15 30 55 90132 315
0.5
1
0.3
0.15
0.08
0.06
0.05
0.04
0.03
0.02
0.015
0.01
0.1
Switching
cycles
x10
6
C3 7
10 14
19
22 30
43
63
Example: 4kW C10: 3.5x10
6
switching cycles (= 350 thousand)
Max
120
ops/hr