R22 & MCS

T ECHN I CA L DATA

246

SPECIFICATION R22 PUSH-BUTTON UNITS

l

Conventional thermal current(

I

th

) -

open

12

A

-

enclosed 10A

Rated operating current (AC15)

V

120

240

380

480

500

600

A

6

3

1.9

1.5

1.4

1.2

Rated operating current (DC15)

V

12

250

440

500

600

A

1.1

0.55

0.31

0.27

0.2

Cable termination - min conductor size

1

x 0.5mm

2

-

max conductor size

2

x 2.5 or 1 x 3.3mm

2

Back-up protection HRC fuse gG

10

A

Ambient temperature limits - operation

˚C -20 to +55

-

storage

˚C -30 to +70

Standards (type tests)

IEC947-5-1, BS EN60947-5-1

MCS SPECIFICATION DATA

l

RATING IN AMPS

16

A 25A 32A 40A 63A 80A

Rated Insulation Voltage Ui (V)

800 800 800 800 800 800

Dielectric Strength (kV) 50 Hz 1min

3

3

3

3

3

3

Shock Resistance Uimp (kV)

8

8

8

8

8

8

OPERATIONAL CURRENT Ie (A)

415

V AC - AC 21 A / AC 21 B

16 25 32 40 63 80

AC 22 A / AC 22 B

16 25 32 40 63 80

AC 23 A / AC 23 B

16 25 32 40 63 80

500

V AC - AC 21 A / AC 21 B

16 25 32 40 63 80

AC 22 A / AC 22 B

16 25 32 40 63 80

AC 23 A / AC 23 B

16 25 32 40 40 63

690

V AC - AC 20 A / AC 20 B

16 20 32 40 63 80

AC 21 A / AC 21 B

16 20 32 40 63 80

AC 22 A / AC 22 B

16 20 32 40 63 80

AC 23 A / AC 23 B

16 25 25 25 50 50

MOTOR POWER (KW) AC 23

415

V AC

7.5

9 11 11 18.5 22

500

V AC

7.5

9 11 15 22 30

690

V AC

11 11 11 18.5 25 30

OVERLOAD CAPACITY

Fuse rating gG

16 25 32 40 63 80

Short circuit current with

fuses (kA Rms)

50 50 50 50 50 40

Asymetric short time

rating current (kA peak)

6

6

6

6

9

9

Admissible short time

current 1 s. (kA Rms)

1.26 1.26 1.26 1.26 1.5 1.5

MAKING & BREAKING CHARACTERISTICS

Breaking capacity (A Rms)

415

V AC 23 A

128 200 256 320 504 640

Making capacity (A Rms)

415

V AC 23 A

160 250 320 400 630 800

WITHSTAND

Mechanical

(

number of operations) x 1000

100 100 100 100 30 30

Electrical (number of operations at

415

V AC 23A) x 1000

3

3

3

3 1.5 1.5

CONNECTION

Maximum Cu cable section (mm

2

)

Ith

16 16 16 16 50 50

INSTALLATION CONTACTORS

l

1 3 5

2 4 6

1 3 5

2 4 6

1 3 5

2 4 6

CONNECTION DIAGRAMS

l

Control circuit

Single Pole

Double Pole

Triple Pole

230

V 50/60 Hz AC

Rectified Coil

TIME CURRENT CHARACTERISTIC CMS25

l

MANUAL MOTOR STARTERS

l

3

pol.

2

pol.

100

x

l

e

50 30 20

1086 43 2

1

0,001

0,002

0,005

0,01

0,02

0,05

0,1

0,2

0,5

1

2

5

10

20

50

100

200

500

1000

x setting current

Ambient temperature 20ºC

Mean values of operating times for CMS 25

Operating time (s)