TECHN I CAL DATA

MOTOR P ROT ECT I ON & CAB L E S P R EAD I NG

240

Motor Approx. Full Load

Direct On Line

Star/Delta

Rating

Current (A)

MCCB Rating/Type

MCCB Rating/Type

HP KW @ 415V G J JM LS/LH N G J JM LS/LH N

10 7.5 14 25 25 – – – 25 25 – – –

12.5 9 17 25 25 – – – 25 25 – – –

15 11 21 25 25 – – – 25 25 – – –

20 15 28 32 32 – – – 32 32 – – –

25 19 35 40 – – – – 40 40 – – –

30 22 41 50 – 50 – – 50 50 50 – –

40 30 52

63 – 63 – – 63 63 63 – –

50 37 69 – – 80 – – – 80 80 – –

60 45 80 – – 100 – – – 100 100 – –

75 55 97 – – 125 – – – 125 125 – –

100 75 125 – – 160 – – – 160 160 – –

125 90 156 – – – 250 – – – 200 – –

150 112 190 – – – 315 – – – – 250 –

175 130 225 – – – 315 – – – – 315 –

200 149 255 – – – 315 – – – – 315 –

220 160 275 – – – 400 – – – – 400 –

250 186 320 – – – 400 – – – – 400 –

300 224 375 – – – 500 – – – – 500 –

350 261 449 – – – 630 600 – – – 630 600

400 298 505 – – – 630 600 – – – 630 600

The figures shown are based on motor starting conditions.

Direct online 7 x full load current for 5 seconds.

Star/Delta 4 x full load current for 12 seconds.

100

200

300

50

100

150

200

CAPACITOR SIZE (kVAr)

250

300

350

400

500

600

700

CIRCUIT BREAKER CURRENT (A)

MOTOR PROTECTION

CAPACITOR CIRCUIT

Circuit breakers are widely used to protect circuits containing

capacitors. Because of circuit harmonics and high “in rush” transients

associated with capacitor circuits it is necessary to select a circuit

breaker with a current rating not less than 1.5 times the capacitor

current.

Powerstar circuit breakers are suitable for off load switching

of capacitors only.

Cable Size

Dimension ‘A’

(

mm

2

)

(

mm

2

)

16

103

25

127

35

142

50

167

70

197

95

224

120

245

150

272

185

297

240

333

300

375

A

4

CORE TERMINATIONS, SPREADING ROOM

BS5372 SPREADING ROOM

The scope of BS5372 relates to dimensions which should be observed

in the design of cable terminations, having uninsulated conductor fittings,

for external cables on electrical equipment to enable the cables to be

connected satisfactorily.

The standard is based upon the use of compression type conductor

terminations and allows for the cores to be crossed within the terminal

enclosure because this combination requires more space.

The diagram and table below gives the dimensions quoted by this standard.

l