Background Image
Table of Contents Table of Contents
Previous Page  80 / 133 Next Page
Information
Show Menu
Previous Page 80 / 133 Next Page
Page Background

TECHN I CAL DATA

MCB AP P L I CAT I ON

218

Crabtree circuit breakers are generally designed for use on ac systems, but

can also be used on dc supplies. The selection of the most suitable circuit

breaker depends on the following conditions:

The type of circuit

The circuit time constant

The short circuit current

The circuit voltage

TYPICAL CIRCUITS

l

POLESTAR MCB APPLICATIONS – DC SUPPLIES

l

NORMAL CIRCUIT CURRENTS

l

The rating and normal running temperature of the MCB are unaffected by dc.

The MCB can be selected using the thermal section of the standard time/

current curves in the normal manner.

Magnetic tripping on dc is different from the equivalent ac by a factor of

2.

ie type B ac magnetic range = 3–5I

n

type B dc magnetic range =

2(3–5)

I

n

= 4–7I

n

type C ac magnetic range = 5–10I

n

type C dc magnetic range =

2(5–10)

I

n

= 7–14I

n

type D ac magnetic range = 10–20I

n

type D dc magnetic range =

2(10–20)

I

n

= 14–28I

n

SHORT CIRCUIT CURRENTS

l

The maximum short circuit current possible on a dc system is determined by

the voltage of the battery and the total internal resistance of the cells. It is

given by Ohm’s law:

I

SC

=

V

b

where V b is the voltage of the battery (with the battery 100% charged)

R b is the internal resistance of the battery cells

R b

(

this is usually quoted by the manufacturer)

CIRCUIT TIME CONSTANT

l

The time constant is given by:

L

where L is the inductance of the circuit

R is the resistance of the circuit

The time constant is usually given in milliseconds (ms). Ideally, dc circuits

would be mainly resistive (ie a low number), as inductive circuits produce a

back emf when the current suddenly falls. This in turn tends to prolong arcing

during switching operations, and so reduces contact life.

CIRCUIT VOLTAGE

l

The voltage of the circuit is dependent upon the power supply. The lower the

voltage the easier switching operations will be, but the voltage makes no

difference to the normal running of the MCBs.

Contact life can be significantly increased by reducing the voltage drop across

each pole. This can be achieved by wiring poles in series. It is also

recommended that for frequent switching the voltage across each pole

should not exceed 110V dc.

Crabtree Polestar MCBs have been successfully tested on dc and can

be used under the following conditions:

Circuit Time Constant L/R 15ms max

Voltage

24–220

V

Short circuit breaking capacity 9kA

C50 MCBs are not suitable for dc circuits and must not be used.

U

F1

F2

F3

Load

E

NOT EARTHED

FAULT F1

Will produce the maximum short circuit current with half the supply

voltage dropped across each pole

FAULTS F2 & F3

No effect

U

F1

F2

F3

Load

E

EARTHED AT THE SUPPLY CENTRE POINT

FAULT F1

Will produce the maximum short circuit current with half the supply

voltage dropped across each pole

FAULTS F2 & F3

Will produce a short circuit current of less than the maximum.

Half the supply voltage will appear across the affected MCB

U

F1

F2

F3

Load

E

EARTHED AT ONE OF THE SUPPLY TERMINALS

FAULT F1

Will produce the maximum short circuit current with half the supply

voltage dropped across each pole

FAULT F2

Will produce the maximum short circuit current with all of the supply

voltage appearing across one pole

FAULT F3

No effect

R

b

R

POLESTAR & LOADSTAR MCB APPLICATIONS – MOTOR STARTERS

l

In general miniature circuit breakers by themselves can only provide short

circuit protection for motor loads.

Motor start-up currents can be as high as 12 times the normal running

current. MCBs in general cannot accommodate this and provide the close

thermal protection required by motors.

They can, however, be used to protect lightly loaded motors or motors

started off load, or they can be used in conjunction with thermal overload

relays. In this case the MCB will protect the cable to the motor against short

circuit faults, and the motor will be protected by a second thermal device.

RECOMMENDED TYPE D MCB RATINGS

for single phase 230/240V ac motors

Motor power

Normal running Start-up

MCB current

HP kW

current (A)

current (A)

rating (A)

0.25 0.18

1.5

18

6

0.50 0.37

3.0

36

6

0.75 0.55

4.5

54

6

1.00 0.75

5.5

66

10

1.50 1.1

8.5

102

10

2.00 1.5

10.5

126

16

3.00 2.2

15.5

186

20

4.00 3.0

20.0

240

32

5.00 3.75

24.0

288

32

7.50 5.5

34.0

408

40

10.00 7.5

45.0

540

63

RECOMMENDED TYPE D MCB RATINGS

for 3 phase 400/415V ac motors

Motor power

Normal running Start-up

MCB current

HP kW

current (A)

current (A)

rating (A)

0.25 0.18

0.7

8.4

6

0.5 0.37

1.35

16.2

6

0.75 0.55

1.55

18.6

6

1.0 0.75

1.93

23.2

6

1.5 1.1

2.5

30.0

6

2.0 1.5

3.5

42.0

6

3.0 2.2

4.8

57.6

6

4.0 3.0

6.4

76.8

10

5.0 3.75

7.8

93.6

10

7.5 5.5

11.0

132.0

16

10.0 7.5

14.4

172.8

20

12.5 9.33

17.3

207.6

32

15.0 11.0

21.0

252.0

32

20.0 15.0

28.0

336.0

40

25.0 18.5

35.0

420.0

50

30.0 22.0

40.0

480.0

50

40.0 30.0

54.0

648.0

63