Protecting photovoltaic systems

Photovoltaic (PV) systems are at risk from

transient overvoltages which may enter the

system following a direct lightning strike to a

structural LPS, or via the wider electrical

network.

Protection against transient overvoltages is achieved

through installation of appropriate SPDs on the DC

and AC side of the DC-AC inverter in the PV system.

Installation should follow the guidance provided in

Technical Specification DD CLC/TS 50539-12.

Installation on the DC side of the DC-AC inverter

An SPD specifically designed for use on the DC side of a

PV system should be installed.

Where the distance between the PV array and the

inverter is < 10 m, a single SPD suffices, mounted as

close as possible to the inverter. Where the distance

> 10 m, two SPDs should be installed, one close to the

inverter and the other close to the PV array. The

minimum Type of SPD is dependent on presence of

structural LPS/separation distance (see Table 4, below).

Note: Furse ESP PV Series SPDs (see pages 250-251)

offer combined Type 1+2 protection, and therefore

apply across all scenarios.

Installation on the AC side of the DC-AC inverter

The presence (or lack) of a structural LPS, plus whether

sufficient separation distance has been kept between

the LPS and the PV array, defines the SPD requirement

on the AC side of the inverter (see Table 4).

Where the distance between service entrance

(Main Distribution Board (MDB)) and inverter is

< 10 m, a single SPD should be installed at the

service entrance (MDB). Where > 10 m, two

SPDs should be installed, one at the MDB and

the other close to the inverter.

Furse Combined Type SPDs for AC mains

power circuits are applicable here. The SPD to

be installed will be dependent on the Class of

LPS around the structure, and the location of

the metallic services connected to it (i.e.

underground/exposed overhead supply).

Selection of the appropriate Furse SPD

therefore follows the product selection chart

shown on page 181.

SPD

SPD

SPD for PV systems

(ESP DC550/12.5/PV or

ESP DC1000/12.5/PV)

AC

Output

Equipotential

bonding bar

DC

Input

kWh kWh

SPD

SPD for AC mains

power (Type 2)

SPD for AC mains power (Type 2)

LV Incomer

Earthing

conductor

Earth

termination

system

Meter/main

distribution

SPD

SPD

SPD for PV systems

(ESP DC550/12.5/PV or

ESP DC1000/12.5/PV)

AC

Output

Equipotential

bonding bar

DC

Input

kWh kWh

SPD

SPD for AC mains power

(Type 2 - separation distance kept)

(Type 1 - separation distance

not kept)

SPD for AC

mains power

(Type 1)

LV Incomer

Earthing

conductor

External LPS

s

s = separation distance.This installation shows the separation distance is kept.Where the

separation distance is not kept, the PV array should be bonded directly to the external LPS.

Earth

termination

system

Meter/main

distribution

s

Generator junction box - SPD for

PV systems (ESP DC550/12.5/PV)

SPD for AC mains

power (Combined

Type 1+2)

Operation building - SPD

for PV systems (ESP DC1000/12.5/PV)

PV units

LPZ 0

Figure 9: Roof

mounted PV

array, no

external LPS

Figure 10:

Roof mounted

PV array,

external LPS

Figure 11: Protection of solar park/PV array

PV arrays should

be protected by a

structural LPS

in line with

BS EN/IEC 62305.

Status of

structural LPS

SPD requirement

Important note:

This page refers to

protection of PV power

circuits only. Ensure any

data/signal/telecoms lines

connected to the PV system

are also appropriately

protected.

Table 4: SPD requirement

according to structural LPS

configuration.

DC side, distance PV array to inverter

AC side of inverter

< 10 m

> 10 m

No structural LPS

ESP PV Series protector

See pages 250-251

(min. Type 2 performance)

ESP PV Series protector

(min. Type 2 performance)

ESP AC mains power protector

See pages 182-195

(min. Type 2 performance)

Structural LPS (separation

distance kept)

ESP PV Series protector

(min. Type 2 performance)

ESP PV Series protector

(min. Type 2 performance)

ESP AC mains power protector

(min. Type 2 performance - inverter)

(min. Type 1 performance - MDB)

Structural LPS (separation

distance not kept)

ESP PV Series protector

(min. Type 1 performance)

ESP PV Series protector

(min. Type 1 performance)

ESP AC mains power protector

(min. Type 1 performance)