Background Image
Table of Contents Table of Contents
Previous Page  173 / 300 Next Page
Information
Show Menu
Previous Page 173 / 300 Next Page
Page Background

Furse, Wilford Road, Nottingham, NG2 1EB • Tel: +44 (0)115 964 3700 • Email:

enquiry@furse.com

• Web:

www.furse.com

TSC-0912 - 09.10.12

Installation

The performance of SPDs is heavily dependent upon

their correct installation. Thus, it is vital that SPDs are

supplied with clear installation instructions.

The following is intended to supplement the detailed

guidance given with each product in order to give a

general overview of installation.

This should not be viewed as a substitute for the

Installation Instructions supplied with the SPD. Copies

of these are available separately on request.

Installing parallel connected SPDs for mains

power supplies:

SPDs should be installed very close to the power

supply to be protected, either within the

distribution panel or directly alongside of it (in

an enclosure to the required IP rating)

Connections between the SPD and phase(s), neutral

and earth of the supply should be kept very short

(ideally 25 cm or less, but no more than 50 cm)

SPD performance is further enhanced by tightly

binding connecting leads together (simply using

cable ties or similar), over their entire length

For safety and convenient means of isolation, the

phase/live connecting leads should be suitably

fused using HRC fuses or switchfuse, MCB or MCCB

Installing in-line SPDs for data, signal, telephone

or power:

SPDs are usually installed between where cabling

enters or leaves buildings and the equipment being

protected (or actually within its control panel)

The installation position should be close to the

system’s earth star point (usually the mains power

earth) to enable a short and direct connection

to earth

In-line, or series, connected SPDs generally have

connections marked line and clean.

The line end of the SPD should be connected to the

incoming or “dirty” line (from where the transient

is expected).

The clean end of the SPD should be connected to

the line or cable feeding the equipment

Cables connected to the SPD’s clean end should

never be routed next to dirty line cables or the

SPD’s earth bond

Unless ready-boxed, SPDs should be installed

within an existing cabinet/cubicle or in an

enclosure to the required IP rating

Note: further information on the satisfactory

installation of SPDs on mains power supplies, to

meet the requirements of IET Wiring Regulations

17th Edition, BS 7671:2008(+A1:2011), can be found

on page 288.

How to apply protection

Transient overvoltages are conducted into the sensitive

circuitry of electronic equipment on power and data

communication, signal and telephone lines. Protection

is recommended for:

all cables which enter or leave the building (except

fibre optic)

the power supply local to important equipment

electronic equipment outside the main building(s)

Protect incoming and outgoing

electrical services

Lightning strikes between clouds or to ground (and

objects upon it) can cause transient overvoltages to be

coupled on to electrical cables, and hence into the

sensitive electronic equipment connected to them.

To protect the electronic equipment inside a building,

all cables that enter or leave the building must be

protected. Cables leaving the building can also provide

a route back into the building for transients.

For each building protect incoming/outgoing:

mains power supplies (including UPS supplies)

data communication and local area network cables

signal, control, instrumentation and alarm lines

CCTV, satellite, TV and antenna cables

telephone and telemetry lines

Protect the power supply locally to

important equipment

In addition to installing protection on the mains power

supply as it enters/leaves the building, protection

should also be installed locally to important

equipment. Protection at the main LV (low voltage)

incomer(s) is necessary to prevent large transients from

entering the building’s power distribution system,

where they could have farreaching effects.

However, where the cable run to equipment exceeds

10 metres (to BS 7671 Clause 534.2.3.1.1), transient

overvoltages may appear on the mains after the

protector at the main LV incomer. These transients can

result from:

the electrical switching of large inductive loads

within the building

a lightning strike to the building - as lightning

currents flow through down conductors transient

overvoltages can be induced on to nearby power

cables

the natural inductance and capacitance of long

cable runs, `amplifying’ the voltage `let-through’

the protector at the main LV incomer

Additionally, local protection guards against the

possibility of a supply which enters/leaves the building

being overlooked and left unprotected.