Background Image
Table of Contents Table of Contents
Previous Page  170 / 300 Next Page
Information
Show Menu
Previous Page 170 / 300 Next Page
Page Background

Table 1: Standardized test waveforms with peak currents used to test

SPDs at each LPZ boundary

SPD location/LPZ boundary

LPZ 0/1

LPZ 1/2

LPZ 2/3

Typical SPD

installation

point

Service Entrance

(e.g. Main

distribution board

or telecom NTP)

Sub-distribution

board

or telecom PBX

frame

Terminal

Equipment

(e.g. socket

outlet)

Mains Test

Class/SPD Type

1

I/1

II/2

III/3

Surge test

waveform

10/350 current

8/20 current

Combination

8/20 current and

1.2/50 voltage

Typical peak

test current

(per mode)

25 kA

2

40 kA

3 kA (with 6 kV)

Signal/Telecom

Test Category

1

D1

3

C2

3

C1

Surge test

waveform

10/350 current

Combination

8/20 current and

1.2/50 voltage

Combination

8/20 current and

1.2/50 voltage

Typical peak

test current

(per mode)

2.5 kA

2 kA (with 4 kV) 0.5 kA (with 1 kV)

1

Tests to BS EN 61643 series

2

Peak current (per mode) for a 3 phase SPD to protect a TN-S mains system

3

Test category B2 10/700 voltage waveform (also within ITU-T standards)

up to 4 kV peak also permissible

Furse, Wilford Road, Nottingham, NG2 1EB • Tel: +44 (0)115 964 3700 • Email:

enquiry@furse.com

• Web:

www.furse.com

TSC-0912 - 09.10.12

What transients are and why you need protection

Figure 7 illustrates the basic LPZ concept defined by

protection measures against LEMP as detailed in

BS EN/IEC 62305-4.

Equipment is protected against both direct and

indirect lightning strikes to the structure and

connected services, through the use of Surge

Protection Measures (SPM), formerly referred to as a

LEMP Protection Measures System (LPMS).

To achieve this reduction in LEMP severity, from

conducted surge currents and transient overvoltages,

as well as radiated magnetic field effects, successive

zones use a combination of shielding measures,

bonding of incoming metallic services such as water

and gas and the use of coordinated SPDs (further

details can be found in the Furse Guide to BS EN 62305

Protection against Lightning).

Given that the live cores of metallic electrical services

such as mains power, data and telecom cables cannot

be bonded directly to earth wherever a line penetrates

each LPZ, a suitable SPD is therefore needed.

The SPD’s characteristics at the boundary of each given

zone or installation location need to take account of

the surge energy they are to be subject to as well as

ensure the transient overvoltages are limited to safe

levels for equipment within the respective zone.

Types of SPD

BS EN/IEC 62305 deals with the provision of SPDs to

protect against both the effects of indirect lightning

strikes and high-energy direct lightning strikes.

Direct lightning strikes are protected by lightning

current or equipotential bonding SPDs (Mains Type

1 SPDs & Signal/Telecom SPDs to Test Category D)

Indirect lightning strikes and switching transients

are protected by transient overvoltage SPDs (Mains

Type 2 and Type 3 SPDs and Signal/Telecom SPDs to

Test Category C)

Lightning current or equipotential bonding SPDs

Lightning current/equipotential bonding SPDs

are designed to prevent dangerous sparking caused

by flashover.

Flashover is caused when the extremely high voltages

associated with a direct lightning strike breaks down

cable insulation. This can occur between the structural

LPS and electrical services and presents a potential fire

hazard and risk from electric shock.

Table 1, above, details the standardized test

waveforms with peak currents used to test SPDs

typically located at each zone boundary.

Boundary

of LPZ 2

(shielded room)

Boundary

of LPZ 1

(LPS)

Antenna

Electrical

power line

Water pipe

Gas pipe

Telecoms

line

Mast or

railing

LPZ 2

B

B

B

B

LPZ 1

Critical

equipment

Equipment

SPD 1/2 - Overvoltage protection

Connected service directly bonded

SPD 0/1 - Lightning current protection

Equipment

LPZ

0

Figure 7: Basic LPZ concept - BS EN/IEC 62305-4