Table of Contents Table of Contents
Previous Page  16 / 73 Next Page
Information
Show Menu
Previous Page 16 / 73 Next Page
Page Background

15

Supply characteristics,

a

24 V products

Type

SR2 

p

121B

SR2 

p

201B

SR3 B101B

SR3 B261B

Nominal voltage

V

a

24

Voltage limits

V

a

20.4…28.8

Nominal frequency

Hz

50-60

Nominal input current

Without extensions

mA

145

233

160

280

With extensions

mA

280

415

Power dissipated

Without extensions

VA

4

6

4

7,5

With extensions

VA

7.5

10

Micro-breaks

Permissible duration

ms

y

10 (repeated 20 times)

rms insulation voltage

V

a

1780

Discrete input characteristics,

a

24 V products

Type

SR

p pppp

B

Nominal value of inputs

Voltage

V

a

24

Current

mA

4.4

Frequencies

Hz

47...53 and 57...63

Input switching limit values

At state 1

Voltage

V

u a

14

Current

mA

> 2

At state 0

Voltage

V

y a

5

Current

mA

< 0.5

Input impedance at state 1

K

4.6

Response

time

LADDER

language

State 0 to 1 (50/60 Hz)

ms

50

State 1 to 0 (50/60 Hz)

ms

50

FBD

language

State 0 to 1 (50/60 Hz)

ms

50 min., 255 max. (in increments of 10)

State 1 to 0 (50/60 Hz)

ms

50 min., 255 max. (in increments of 10)

Isolation

Between supply and inputs

None

Between inputs

None

Protection

Against inversion of terminals

Yes (control instructions not executed)

Relay output characteristics,

a

24 V products

Type

SR2 

p

121B

SR3 B101B

SR3 XT101B

SR2 

p

201B

SR3 B261B SR3 XT61B SR3 XT141B

Operating limit values

V

c

5...30,

a

24...250

Contact type

N/O

Thermal current

A

4 outputs: 8 A 8 outputs: 8 A 8 outputs: 8 A

2 outputs: 5 A

2 outputs: 8 A 4 outputs: 8 A

2 outputs: 5 A

Electrical durability for

500 000 operating cycles

Conforming to

IEC/EN 60947-5-1

Utilisation

category

DC-12

V

c

24

A

1.5

DC-13

V

c

24 (L/R = 10 ms)

A

0.6

AC-12

V

a

230

A

1.5

AC-15

V

a

230

A

0.9

Minimum switching

capacity

At minimum voltage

of

c

12 V

mA

10

Low power switching

reliability of contact

c

12 V - 10 mA

Maximum operating rate

No-load

Hz

10

At Ie (operational current)

Hz

0.1

Mechanical life

In millions of operating cycles

10

Rated impulse

withstand voltage

Conforming to IEC/EN 60947-1

and IEC/EN 60664-1

kV

4

Response time

Set

ms

10

Reset

ms

5

Built-in protection

Against short-circuits

None

Against overvoltage and

overload

None

Presentation :

pages 6 to 9

Functions :

pages 10 to 12

Curves :

pages 20 and 21

References :

pages 22 to 27

Dimensions, schemes :

pages 28 to 31

Characteristics

(continued)

1

Zelio Logic smart relays

1

Compact and modular smart relays

1

2

3

4

5

6

7

8

9

10