19

Relay output characteristics,

c

24 V products

Type

SR2 

p

101BD

SR2 

p

121BD

SR3 B101BD

SR3 XT101BD

SR2 

p

201BD SR3 B261BD SR3 XT61BD SR3 XT141BD

Operating limit values

V

c

5...30,

a

24...250

Contact type

N/O

Thermal current

A

4 outputs: 8 A 8 outputs: 8 A 8 outputs: 8 A

2 outputs: 5 A

2 outputs: 8 A 4 outputs: 8 A

2 outputs: 5 A

Electrical durability for

500 000 operating cycles

Conforming to

IEC/EN 60947-5-1

Utilisation

category

DC-12

V

c

24

A

1.5

DC-13

V

c

24 (L/R = 10 ms)

A

0.6

AC-12

V

a

230

A

1.5

AC-15

V

a

230

A

0.9

Minimum switching

capacity

At minimum voltage

of

c

12 V

mA

10

Low power switching

reliability of contact

c

12 V - 10 mA

Maximum operating rate

No-load

Hz

10

At Ie (operational current)

Hz

0.1

Mechanical life

In millions of operating cycles

10

Rated impulse

withstand voltage

Conforming to IEC/EN 60947-1

and IEC/EN 60664-1

kV

4

Response time

Set

ms

10

Reset

ms

5

Built-in protection

Against short-circuits

None

Against overvoltage and

overload

None

Relay output characteristics,

c

24 V products

Type

SR

p

B

pp

2BD

Operating limit values

V

c

19.2..0.30

Load

Nominal voltage

V

c

24

Nominal current

A

0.5

Maximum current

A

0.625 at 30 V

Residual voltage

At state 1

V

y c

2 for I = 0.5 A

Response time

Set

ms

y

1

Reset

ms

y

1

Built-in protection

Against overload

and short-circuits

Yes

Against overvoltage

Yes

Against inversions of

power supply

Yes

Presentation :

pages 6 to 9

Functions :

pages 10 to 12

Curves :

pages 20 and 21

References :

pages 22 to 27

Dimensions, schemes :

pages 28 to 31

Characteristics

(continued)

1

Zelio Logic smart relays

1

Compact and modular smart relays

1

2

3

4

5

6

7

8

9

10